Page 108 - B_ELSB_Cat_2022_01_MCBs
P. 108

1/108            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          Coordination tables: selectivity




          S800S - S200 M @ 230/400 V
                           E.    S800S
                 Char.           B
          L.          Icu [kA]   50
                           In [A]  25      32        40        50       63        80        100       125
                           6                         0.4       0.5      0.7       1         1.5       2.6
                           10                                  0.4      0.6       0.7       1         1.4
                           13                                           0.5       0.7       0.9       1.3
                           16                                                     0.7       0.9       1.3
                           20                                                               0.9       1.3
          S200M  B   15
                           25                                                               0.9       1.3
                           32                                                               0.8       1.1
                           40                                                               0.8       1.1
                           50                                                                         1
                           63                                                                         0.9


                           E.    S800S
                 Char.           B
          L.          Icu [kA]   50
                           In [A]  25      32        40        50       63        80        100       125
                           0.5   T         T         T         T        T         T         T         T
                           1     3.3       T         T         T        T         T         T         T
                           1.6   0.6       1.3       T         T        T         T         T         T
                           2     0.4       0.7       1.3       T        T         T         T         T
                           3               0.4       0.6       0.7      1.1       2.6       8.8       T
                           4               0.4       0.6       0.7      1         1.7       3.1       7
                           6                         0.4       0.5      0.7       1         1.5       2.6
                           8                                   0.4      0.6       0.7       1         1.4
          S200M  C   15    10                                  0.4      0.6       0.7       1         1.4
                           13                                           0.5       0.7       0.9       1.3
                           16                                                     0.7       0.9       1.3
                           20                                                               0.9       1.3
                           25                                                               0.9       1.3
                           32                                                               0.8       1.1
                           40                                                               0.8       1.1
                           50                                                                         1
                           63                                                                         0.9



















         E. = feed side
         L. = load side
         T  = Total selectivity up to breaking capacity of the switch on load side
             Selectivity limit values indicated in kA
   103   104   105   106   107   108   109   110   111   112   113