Digiware DC Metering System



        DIRIS DIGIWARE VOLTAGE MODULES


                                               DC VOLTAGE MEASUREMENT MODULES
        Features:                               Description                                          Part No.
           - Single voltage measurement point for the
          entire system                         Metering Application
           - Single point of protection for the voltage   U-31dc voltage module                      48290150
          measurement                           U-32dc voltage module                                48290151
           - No hazardous voltage on panel doors
           - The voltage adaptors makes the system compatible
          with all DC electrical networks
           - Plug and play, easy to configure
           - Complies with standard IEC 61557-12
                                               DC VOLTAGE MEASUREMENT MODULE SELECTION CHART
                                                                                      U-31dc        U-32dc
                                                Nominal Voltage Range                 24 - 48V DC   60 - 150V DC
                                                Measuring Range (Minimum - Maximum)   19.2 - 60V DC  48 - 180V DC
                                                Multi-measurement
                                                DC voltage (V DC)                     •             •
                                                Power Quality
                                                V ripple (voltage ripple)             •             •
                                                Vrms                                  •             •
                                                Alarms
                                                Thresholds and combinations           •             •
                       48290151
                                                Trends
                                                Average values                        •             •







                                               DC VOLTAGE ADAPTORS

                                                                                   Maximum Voltage
                                                To Suit          Description                         Part No.
                                                                                   Range
                                                                 U500dc            200 - 600V DC     48290153
                                                U-32dc           U1000dc           400 - 1200V DC    48290154
                                                                 U1500dc           1200 - 1650V DC   48290155