Page 288 - IPD Product Catalog V17
P. 288

Current Transformers



        EXTENDED RANGE SUPPLY AUTHORITY CURRENT TRANSFORMERS


                                               NER COMPLIANT SOLID CORE CURRENT TRANSFORMERS
        Features:                                                  Class 0.5S
           - Type tested to IEC 61869-2:2012    Current Ratio      VA              Type              Part No.
           - Compliant to National Electricity Rules (NER)  200/5  5               S                 SCT200-IPD
          requirements                          800/5              15              T                 TCT800-IPD
           - Routine tested to IEC 61869-2:2012  1500/5            15              W                 WCT1500-IPD
           - Routine test compliance report included with
          each CT
           - Extended range
           - All models include tunnel terminals
           - Mounting brackets and terminal cover included
           - Cast resin encapsulated
           - Class 0.5S
                                               SPECIFICATIONS
                                         >
                                                                        Type S           Type T      Type W
                                        >       Class                   0.5S             0.5S        0.5S
                                         153
                                      >  130    Insulation Class        E                E           E
                                      45
                                                Dielectric Strength (kV/min)  2.5        2.5         2.5
                                      >
                                         >
                                       >
                                >
                         53 >  >  65            Nominal Frequency (Hz)  50/60            50/60       50/60
                                                Nominal Voltage (AC Primary) (V) 660     660         660
                                >
                       SCT200-IPD               Degree of Protection    IP40             IP40        IP40
                                                Short Time Current      40kA/0.5s        50kA/0.5s   50kA/1s
                                            >
                                          >
                                           205
                                         >  177
                                        85     RANGE OF LOADING
                                        >
                                            >
                                                Type                                            IEC 61869-2:2012
                                          >
                                 >
                        60 >     88             ‘S’                                             2A to 400 A
                        >
                                                ‘T’                                             8A to 1600A
                                 >
                                                ‘W’                                             15A to 3000A
                       TCT800-IPD
                                             >
                                           >
                                            205  DIMENSIONS
                                         >  177
                                        114                                        Diameter
                                                Type             Axias Length (mm)
                                         >
                                                                                   Outer (mm)        Inner (mm)
                                            >
                                          >
                                  >
                        60 >     88             ‘S’              53                130               45
                        >
                                                ‘T’              60                177               85
                                 >
                                                ‘W’              60                177               114
                      WCT1500-IPD

















          288                                    1300 556 601  |  ipd.com.au  |  V17-R05
   283   284   285   286   287   288   289   290   291   292   293