Page 316 - IPD Product Catalog V17
P. 316

Meters



        NMI/SUB-BILLING METER SELECTION CHART

                                          Single phase           Three phase            Three phase
         Network - Input Current          Direct Connect, 63A    Direct Connect, 100A   CT Connect, 5A


         Energy and Sub-billing meters


         References                       IPD163C                IPD3100C               IPD3005C
         Main Specifications
         Complies with NMI requirements and
         is certified for trade use (billing applications)  Approved  Approved          Approved
         Self powered                     •                      -                      -
         Width (18mm)                     2 Module               7 Module               7 Module
         Real-time Measurements
         Uln/Ull per phase and Average    •                      •                      •
         Current per phase and Average, In  •                     •                      •
         kW/kvar/kVA per phase and Total   •                      •                      •
         PF per phase and Total            •                      •                      •
         Frequency                         •                      •                      •
         Demands and Peak Demands          •                      •                      •
         Energy Measurements (per phase and 3-phase total)
         Active energy kWh Imp, Exp, Net, Total  •                •                      •
         Reactive energy kvarh Imp, Exp, Net, Total  •            •                      •
         Apparent energy kVAh Total        •                      •                      •
         4-Quadrant kvarh                  -                      •                      •
         TOU Energy (4 Tariffs)            -                      •                      •
         Power Quality
         Voltage and Current Unbalance     •                      •                      •
         THD, THOD, THED, K-Factor, Crest-Factor, TDD  -          •                      •
         Individual Harmonics (2  to 31 )  -                     •                      •
                             st
                         nd
         Logging
         Max./Min. & Peak Demand Recording  -                    •                      •
         12 Month Energy Log              -                      •                      •
         SOE Log                          -                      •                      •
         Data Recorder Log with 2MB Memory  -                    •                      •
         Inputs and Outputs
         Digital Inputs                   -                      3                       3
         Energy Pulse Output (Solid State Relay)  1               1                      1
         Metrological LED Energy Pulse Output  1                  1                      1
         Communications
         RS485 Modbus RTU                  •                      •                      •
         Real-time Clock
         Battery-backed real-time clock at 6ppm  -                •                      •
         Clock error ≤ 0.5s/day            -                      •                      •
         Can be set through front panel or   -                    •                      •
         communication
         System Integration
         Easy integration into other Automation or   -            •                      •
         SCADA systems
         Accuracy
         Active energy (IEC 62053-21)      1                      1                      0.5S (According to IEC 62053-22)
         Reactive energy (IEC 62053-23)    2                      2                      2







          316                                    1300 556 601  |  ipd.com.au  |  V17-R05
   311   312   313   314   315   316   317   318   319   320   321