Page 316 - IPD Product Catalog V17
P. 316
Meters
NMI/SUB-BILLING METER SELECTION CHART
Single phase Three phase Three phase
Network - Input Current Direct Connect, 63A Direct Connect, 100A CT Connect, 5A
Energy and Sub-billing meters
References IPD163C IPD3100C IPD3005C
Main Specifications
Complies with NMI requirements and
is certified for trade use (billing applications) Approved Approved Approved
Self powered • - -
Width (18mm) 2 Module 7 Module 7 Module
Real-time Measurements
Uln/Ull per phase and Average • • •
Current per phase and Average, In • • •
kW/kvar/kVA per phase and Total • • •
PF per phase and Total • • •
Frequency • • •
Demands and Peak Demands • • •
Energy Measurements (per phase and 3-phase total)
Active energy kWh Imp, Exp, Net, Total • • •
Reactive energy kvarh Imp, Exp, Net, Total • • •
Apparent energy kVAh Total • • •
4-Quadrant kvarh - • •
TOU Energy (4 Tariffs) - • •
Power Quality
Voltage and Current Unbalance • • •
THD, THOD, THED, K-Factor, Crest-Factor, TDD - • •
Individual Harmonics (2 to 31 ) - • •
st
nd
Logging
Max./Min. & Peak Demand Recording - • •
12 Month Energy Log - • •
SOE Log - • •
Data Recorder Log with 2MB Memory - • •
Inputs and Outputs
Digital Inputs - 3 3
Energy Pulse Output (Solid State Relay) 1 1 1
Metrological LED Energy Pulse Output 1 1 1
Communications
RS485 Modbus RTU • • •
Real-time Clock
Battery-backed real-time clock at 6ppm - • •
Clock error ≤ 0.5s/day - • •
Can be set through front panel or - • •
communication
System Integration
Easy integration into other Automation or - • •
SCADA systems
Accuracy
Active energy (IEC 62053-21) 1 1 0.5S (According to IEC 62053-22)
Reactive energy (IEC 62053-23) 2 2 2
316 1300 556 601 | ipd.com.au | V17-R05