Page 586 - IPD Product Catalog V17
P. 586

Contactors & Overloads



        MINI CONTACTORS & OVERLOADS - 4kW TO 5.5kW


                                               4 POLE - MINI CONTACTORS WITH SCREW TERMINALS
        Features:                               Rated Operational  Rated Operational   Rated Control  Main Contacts
           - No. of poles: 4                    Power AC-3 400V   Current AC-1 240V   Circuit        Part No.
           - Add-on auxiliary contact           (kW)          (A)            Voltage (V)  NO   NC
           - Resistive loads up to 690V AC                                              4      0     B6400001
           - DIN Rail or wall mounting                                       24 AC      2      2     B6220001
                                                4             20                        4      0     BC6400001
                                                                             24 DC
                                                                                        2      2     BC6220001
                                                                             220 - 240 AC  4   0     B6400080
                                                                                        4      0     B7400001
                                                                             24 AC
                                                                                        2      2     B7220001
                                                                                        4      0     BC7400001
                                                5.5           20             24 DC
                                                                                        2      2     BC7220001
                       B6400001                                                         4      0     B7400080
                                                                             220 - 240 AC
                                                                                        2      2     B7220080
                                               -  AC1 current ratings are considered at θ ≤ 40°C

                                               THERMAL OVERLOAD RELAYS
        Features:                                                Thermal Current Setting  Short-Circuit Protective
           - Selectable manual or automatic reset  To Suit       Range (A)         Device            Part No.
           - Phase loss sensitive according to                   0.10 - 0.13       0.5A, fuse type T  T16-0.13
          IEC/EN 60947-4-1                                                                           T16-0.17
           - TEST and STOP function – trip indication on the front  0.13 - 0.17    1.0A, fuse type T
           - Temperature compensation                            0.17 - 0.23       1.0A, fuse type T  T16-0.23
           - Suitable for three and single phase applications    0.23 - 0.31       1.0A, fuse type T  T16-0.31
           - Tripping class 10                                   0.31 - 0.41       2.0A, fuse type gG  T16-0.41
                                                                 0.41 - 0.55       2.0A, fuse type gG  T16-0.55
                                                                 0.55 - 0.74       4.0A, fuse type gG  T16-0.74
                                                                 0.74 - 1.00       6.0A, fuse type gG  T16-1.0
                                                B6, BC6, VB6, BC7, B7   1.00 - 1.30  6.0A, fuse type gG  T16-1.3
                                                VB7, VBC6, VBC7, MC1,
                                                MC2              1.30 - 1.70       10.0A, fuse type gG  T16-1.7
                                                                 1.70 - 2.30       10.0A, fuse type gG  T16-2.3
                                                                 2.30 - 3.10       10.0A, fuse type gG  T16-3.1
                                                                 3.10 - 4.20       20.0A, fuse type gG  T16-4.2
                         T16                                     4.20 - 5.70       20.0A, fuse type gG  T16-5.7
                                                                 5.70 - 7.60       35.0A, fuse type gG  T16-7.6
                                                                 7.60 - 10.0       35.0A, fuse type gG  T16-10
                                                                 10.0 - 13.0       40.0A, fuse type gG  T16-13
                                                                 13.0 - 16.0       40.0A, fuse type gG  T16-16


                                               ELECTRONIC OVERLOAD RELAYS
        Features:                                                Thermal Current Setting  Short-Circuit Protective
           - Selectable manual or automatic reset  To Suit       Range (A)         Device            Part No.
           - TEST and STOP function – trip indication            0.10 - 0.32       1A, fuse type gG  E16DU-0.32
          on the front                                           0.30 - 1.00       4A, fuse type gG  E16DU-1.0
           - High accuracy                      B6, B7, BC6, BC7, VB6,   0.80 - 2.70  10A, fuse type gG  E16DU-2.7
                                                VB7, VBC6, VBC7, MC1,
           - Temperature compensation           MC2
           - Trip contact (NC), signal contact (NO)              2.00 - 6.30       20A, fuse type gG  E16DU-6.3
           - Tripping class 10E, 20E, 30E                        5.70 - 18.9       50A, fuse type gG  E16DU-18.9
           - Suitable for three phase application only










                        E16DU


         586                                     1300 556 601  |  ipd.com.au  |  V17-R05