Page 77 - IPD Product Catalog V17
P. 77
Moulded Case Circuit Breakers (MCCB)
COMPATIBILITY OF ACCESSORIES
POSITION OF INTERNAL ACCESSORIES FOR THE TMAX XT5
With 4 pole circuit breakers, it is not possible to add accessories to the fourth pole.
1
YO/YU KLC on CB 1Q+1SY
2Q+1SY 3Q+1SY 1S51
Ekip COM /
1S52 (1) 2Q 400V Ekip COM
(2)
STA /
Micro I/O
Ekip 1K / 1Q+1SY 1Q+1SY
Ekip MM (3) le (4) 400V (4)
(1) YO or YU must be mounted on the third pole to make S52 signaling available
(2) Ekip COM or stand-alone module, depending on the trip unit
(3) Available for the Ekip Touch and Ekip Hi-Touch only
(4) Available for the TM trip unit, Ekip Dip trip unit and switch-disconnector only
READING INFORMATION
Glossary Description Glossary Description
YO : Shunt opening release S52 : Contact signaling YO/YU tripping
YU : Undervoltage release Ekip COM : Ekip Communication module
KLC on CB : Keylock device on circuit breaker Ekip COM STA : Ekip Communication module stand-alone
Q : Contact signaling open/closed Micro I/O : Module for Touch and Hi-Touch trip unit
SY : Contact signaling tripping Ekip 1K : Ekip 1K signaling
S51 : Contact signaling tripping due to trip unit Ekip MM : Ekip Maintenance Module
1300 556 601 | ipd.com.au | V17-R05 77