Arc fault protection
            system DEHNshort



            DEHNshort is a modular arc fault protection system
            which detects arc faults with the help of current and
            light sensors. Thanks to its short response time of a
            few milliseconds, the incident energy is reduced to a
            minimum. DEHNshort takes the protection of persons                            5
            and systems to another level and by far exceeds
            the requirements of the currently applicable IEC TR
            61641* standard.

            Detection:
            The current transformers at the infeed detect the
            overcurrent resulting from the arc fault and transmit this   2                                        4
            information to the relevant detection device. Sensors
            detect the light emitted by the arc fault and also transmit
            this information to the detection device. Depending on
            the application, fibre optic and optoelectronic sensors are
            available.
                                                                                                    1
            Evaluation:
            In the detection devices, the sensor signals are converted
            into digital information and are linked together logically.
            If all arc fault detection criteria are fulfilled, quenching
            and disconnection commands are issued. The quenching
            devices are immediately activated via fibre optic cables, the
            shunt releases via relay contacts. LEDs indicate the current
            status of the system. Since the detection devices are
            integrated in the assembly door, the system status can also
            be evaluated if the assembly door is closed.

            Arc fault quenching:
            In order to quench the arc fault as quickly as possible, the
            detection device activates the relevant quenching devices.
            The current commutates from the arc fault to the low-im-
            pedance bolted short-circuit of the two quenching devices
            and the voltage drops, thus quenching the arc fault. Power
            thyristors ensure short commutation times which cannot
            be achieved by previous solutions.                                 3

            Disconnection:
            At the same time as the quenching devices, the detection
            devices transmit a trip command to the shunt releases of
            all incoming circuit breakers via a floating relay contact
            and disconnect the part of the switchgear assembly where
            the arc fault occurred.

            Recommissioning:
            The switchgear assembly can be recommissioned after the
            fault has been rectified, the quenching devices have been                                           2
            replaced and the arc fault protection system has been
            reset.

















            *   IEC TR 61641: Low-voltage switchgear and controlgear assemblies; Guide for testing under conditions of arcing due to internal fault
            **   IEC 60364-4-42: Low-voltage electrical installations – Part 4-42: Protection for safety – Protection against thermal effects
    6       ***  IEC 60364-5-5: Low-voltage electrical installations – Part 5-53: Selection and erection of electrical equipment – Switchgear and control gear