Page 46 - Application Guide Semiconductor Fuse Link
P. 46
Appendix
(b) typical values of C1 for Ferraz Shawmut fuses
C1
C1
FUSE without liquid with liquid cooling
TECHNOLOGY SIZE TYPE cooling on to keep the fuse
(construction) contacts below 60 °C
terminals
on both sides
30-31-32-33 & doubles UR- 0.85 1.30
gR- 0.85 1.25
70-71-72-73 & doubles UR- 0.90 1.25
gR- 0.90 1.20
83-84 & doubles UR- 0.90 1.20
square gR- 0.90 1.15
91-92-93-94 & doubles UR- 0.90 1.10
gR- 0.90 1.05
120-121-122-123-124 UR- 0.95 1
& doubles gR- 1 1
longer bodies all 1 1
130 V to 300 V 0.80 1.30
round 500 V to 1000 0.85 1.20
fi bre-glass 1100 to 1500 V 0.90 1.10
1600 V to 3000 V 0.95 1
above 3000 V 1 1
A13X(amp)-1 or 2
A13Z(amp)-1 or 2 0,80 1,30
A25X (amp)-1 or 2
A25Z(amp)-1 or 2
A50P(amp)-1,1DS
A70P(amp)-1,1DS
A60X(amp)-1 0,85 1,20
A60Z(amp)-1
A100P(amp)-1,1A
A100X(amp)-1,1A
A100Z(amp)-1,1A
American A70QS(rating)-14F 0,90 1
ferrules 14FI , 22F , 22FI
A60Q(rating)-2 0,90 1
A120X(rating)-2
A150P(rating)-1
A150X(rating)-1 or 1W 0,90 1,1
A150Z(rating)-1 or 1W
European all sizes according to the rated power of the
ferrules fuse-holder : see the de-rating table of
the holder published in the ADVISOR
46