Page 96 - Changeover switch
P. 96

96               ABB  TRANSFER AND CHANGE-OVER SWITCHES




         —
         Technical data

         Compact automatic transfer switches OTM40...125_



         —
         Compact automatic transfer switches
                                                                                                        Switch size
          Data according to IEC 60947-6-1                                         OTM40_     OTM63_      OTM125_
          Class of equipment                                                         PC          PC          PC
          Rated short-time withstand current      Icw (r.m.s.)  690 V 0.1s  kA        5           5           5
          Conditional short-circuit current       Icc (r.m.s.)   415 V    kA         50          50          50
          Corresponding fuse rating              gG/aM fuse      415 V    A          125         125        125
          Rated operational current, AC-31B                  up to 415 V  A          40          63         125
          Rated operational current, AC-32B                  up to 415 V  A          40          63         125
          Rated operational current, AC-33B                  up to 415 V  A          40          63          80
          1)  These values are given for guidance and may vary according to the motor manufacturer
          2)  Short circuit duration > 50ms, without fuse protection
          3)  Operating cycle: O - I - O - II - O
   91   92   93   94   95   96   97   98   99   100   101