Page 234 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 234

3/158            ABB  MOTOR PROTECTION AND CONTROL

          —

          AFS116 ... AFS370  3-pole contactors for safety applications
          Technical data





          Main pole - Utilization characteristics according to UL / NEMA / CSA
   03
          Contactor types         AC / DC operated AFS116  AFS146  AFS190  AFS205  AFS265    AFS305   AFS370
          Standards                         UL 60947-1 / 60947-4-1 and CSA C 22.2 N°60947-1 / 60947-4-1
          Maximum operational voltage       600 V     1000 V
          NEMA size                         –         –         –        –         5         –        –
          NEMA continuous amp rating  Thermal current –  –      –        –         270 A     –        –
          NEMA maximum
          horse power ratings         115 V AC –      –         –        –         –         –        –
          1-phase, 60 Hz              230 V AC –      –         –        –         –         –        –
          NEMA maximum
          horse power ratings         200 V AC –      –         –        –         75 hp     –        –
          3-phase, 60 Hz              230 V AC –      –         –        –         100 hp    –        –
                                      460 V AC –      –         –        –         200 hp    –        –
                                      575 V AC –      –         –        –         200 hp    –        –
          UL / CSA general use rating
            600 V AC                        160 A     200 A     275 A    300 A     350 A     400 A    520 A
            With conductor cross-sectional area  AWG 2/0  AWG 3/0  MCM 250  MCM 350 (2)  MCM 500  2//AWG 3/0  2//MCM 300
            1 000 V AC                      –         200 A     250 A    275 A     300 A     350 A    400 A
            With conductor cross-sectional area  AWG 2/0  AWG 3/0  MCM 250  MCM 350 (2)  MCM 500  2//AWG 3/0  2//MCM 300
            1 pole                     90 V DC 160 A  200 A     –        –         –         –        –
                                      100 V DC –      –         250 A    350 A     –         –        –
                                      110 V DC –      –         –        –         400 A     500 A    520 A
            2 poles in serie          175 V DC 160 A  200 A     –        –         –         –        –
                                      200 V DC –      –         250 A    350 A     –         –        –
                                      225 V DC –      –         –        –         400 A     500 A    520 A
            3 poles in serie          260 V DC 160 A  200 A     –        –         –         –        –
                                      300 V DC –      –         250 A    350 A     –         –        –
                                      340 V DC –      –         –        –         400 A     500 A    520 A
            With conductor cross-sectional area  AWG 2/0  AWG 3/0  MCM 250  MCM 350 (2)  MCM 500  2//AWG 3/0  2//MCM 300
          UL / CSA maximum 1-phase motor rating
            Full load current         120 V AC –      –         –        –         –         –        –
                                      240 V AC –      –         –        –         –         –        –
            Horse power rating        120 V AC –      –         –        –         –         –        –
                                      240 V AC –      –         –        –         –         –        –
          UL / CSA maximum 3-phase motor rating
            Full load current (1)   200-208 V AC 92 A  120 A    150 A    177 A     221 A     285 A    359 A
                                    220-240 V AC 104 A  130 A   154 A    192 A     248 A     312 A    360 A
                                    440-480 V AC 96 A  124 A    156 A    180 A     240 A     302 A    361 A
                                    550-600 V AC 99 A  125 A    144 A    192 A     242 A     289 A    336 A
            Horse power rating (1)  200-208 V AC 30 hp  40 hp   50 hp    60 hp     75 hp     100 hp   125 hp
                                    220-240 V AC 40 hp  50 hp   60 hp    75 hp     100 hp    125 hp   150 hp
                                    440-480 V AC 75 hp  100 hp  125 hp   150 hp    200 hp    250 hp   300 hp
                                    550-600 V AC 100 hp  125 hp  150 hp  200 hp    250 hp    300 hp   350 hp
          Short-circuit protection device for contactors
          without thermal overload relay - Motor protection excluded
            High fault current              100 kA
            Fuse rating                     225 A     250 A     350 A    400 A     500 A     600 A    600 A
            Fuse type, 600 V                J
          Maximum electrical switching frequency
            For general use                 300 cycles/h
            For motor use                   300 cycles/h
          (1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
          (2) For conductor cross-sectional area above MCM 300 use terminal enlargements LW205.