Page 761 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 761
ABB MOTOR PROTECTION AND CONTROL 6/23
—
TF96 thermal overload relays – 40.0 to 96.0 A
Technical data
Main circuit – Utilization characteristics according to UL/CSA
Type TF96
Standards UL 60947-1, UL 60947-4-1
Maximum operational voltage 600 V AC/DC
Trip rating 125% of FLA
Full load amps (FLA) See table "Full load amps and short-circuit protective device"
Short-circuit rating RMS symmetrical See table "Full load amps and short-circuit protective device"
Short-circuit protective device See table "Full load amps and short-circuit protective device"
Auxiliary circuit according to UL/CSA
Type TF96
Contact rating N.C., 95-96 B600, Q600
N.O., 97-98 D300, Q600
Conventional thermal current N.C., 95-96 5 A
N.O., 97-98 2.5 A
Full load amps and short-circuit protective device
Type Full load amps (FLA) Short-circuit protective device 06
480 / 600 V AC 480 / 600 V AC
Short circuit rating RMS Fuse type Short circuit rating RMS Fuse type
symmetrical symmetrical
TF96-51 51 A 5 kA 150 A, K5 / RK5 100 kA 125 A, Class J
TF96-60 60 A 10 kA 150 A, K5 / RK5 100 kA 150 A, Class J
TF96-68 68 A 10 kA 150 A, K5 / RK5 100 kA 150 A, Class J
TF96-78 78 A 10 kA 175 A, K5 / RK5 100 kA 175 A, Class J
TF96-87 87 A 10 kA 200 A, K5 / RK5 100 kA 200 A, Class J
TF96-96 96 A 10 kA 250 A, K5 / RK5 100 kA 200 A, Class J