Page 914 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 914

13/24            ABB  MOTOR PROTECTION AND CONTROL

          —

          DOL starters protected by MCCB including motor protection
          Coordination type 1 or 2




          Coordination type 1 or 2, AC-3, 50 kA, 400 V, 50/60 Hz
                    MCCB                                                                                                          Contactors                                     Connection bars







                                                                   +


          IEC       Magnetic   Max. allowed  Base                            Trip unit                                            Control voltage   Type     Order code          Type       Order code
          AC-3, 400 V  triping   thermal setting  Type  Order code           Type           Order code                            Uc min. ... Uc max.
          Rated   Rated    current
          power  current  setting
          kW   A    A                                                                                                             V 50/60 Hz  V DC
          55   97   1440    116       XT2S 160         1SDA068164R1        +  Ekip M-LIU In160  1SDA067355R1                      24...60   20...60  AF116-30-11-11  1SFL427001R1111  BEA140/XT2  1SFN084206R1000
                                                                                                                                  100...250  100...250  AF116-30-11-13  1SFL427001R1311
          75   132  1920    140       XT2S 160         1SDA068164R1        +  Ekip M-LIU In160  1SDA067355R1                      24...60   20...60  AF140-30-11-11  1SFL447001R1111
                                                                                                                                  100...250  100...250  AF140-30-11-13  1SFL447001R1311
          90   160  2400    190       T4S 250 PR222MP In200  1SDA054527R1    Included       -                                     24...60   20...60  AF190-30-11-11  1SFL487002R1111  BEA205/T4  1SFN084806R1001
                                                                                                                                  100...250  100...250  AF190-30-11-13  1SFL487002R1311
          110  195  2880    205       T5S 400 PR222MP In320  1SDA054553R1    Included       -                                     24...60   20...60  AF205-30-11-11  1SFL527002R1111
                                                                                                                                  100...250  100...250  AF205-30-11-13  1SFL527002R1311
          132  230  3600    265       T5S 400 PR222MP In400  1SDA054554R1    Included       -                                     24...60   20...60  AF265-30-11-11  1SFL547002R1111  BEA370/T5  1SFN085406R1000
                                                                                                                                  100...250  100...250  AF265-30-11-13  1SFL547002R1311
          160  280  4400    305       T5S 400 PR222MP In400  1SDA054554R1    Included       -                                     24...60   20...60  AF305-30-11-11  1SFL587002R1111
                                                                                                                                  100...250  100...250  AF305-30-11-13  1SFL587002R1311





























   13