Page 912 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 912

13/22            ABB  MOTOR PROTECTION AND CONTROL

          —

          DOL starters protected by moulded-case circuit-breakers and overload relays
          With AF contactors - open type version in kit form




                                    Application
                                    Full voltage direct-on-line (DOL) starting for controlling three-phase asynchronous motors
                                    is a simple and economic solution characterised by a high starting torque (1.9 to 2.1 times
                                    full-speed torque) and a starting current 5.5 to 7 times nominal current.
                                    I /In  C /Cn
                                    7
                                    6
                                                I
                                    5
                                                              I = current
                                    4                         C = torque
                                                              In = nominal current
                                    3
                                                              Cn = nominal torque
                                    2
                                            C
                          1SFC101191V0001  0  10  30  60  80  100
                                    1
                                    Coordination types
          XT2S 160 + BEA140/XT2 +    The contactor and the moulded-case circuit-breaker control and protect motors against
          AF140-30-11
                                    overload and short-circuits according to coordination types 1 and 2 (IEC 60947-4-1/
                                    EN 60947-4-1) defining the anticipated level of service continuity as follow:
                                    Type 1:  In short-circuit conditions, the contactor or starter does not endanger persons or in-
                                          stallations and will not be able to then operate without being repaired or having
                                          parts replaced.
                                    Type 2:  In short-circuit conditions, the contactor or starter does not endanger persons or in-
                                          stallations and will be able to operate afterwards. The risk of contacts light welding
                                          is acceptable.

                                    Main Technical Data
                                    Standards                   IEC 60947-4-1 / EN 60947-4-1
                                    Rated operational voltage Ue max.  400 V - 50/60 Hz
                                    Rated insulation voltage Ui
                                      acc. to IEC 60947-4-1     690 V
                                      acc. to UL / CSA          600 V
                                    Switching frequency         ≤ 15 starts/hour - 80 % max. load factor - with max. 1.5 s starting time
                                                                ≤ 30 starts/hour - 50 % max. load factor - with max. 1.5 s starting time
                                    Ambient air temperature
                                      Close to the device       < 55 °C

                         1SFC101190V0001  Degree of protection  IP20





                                    Mounting positions
          XT2S 160 + BEA140/XT2 +
          AF140-30-11 + EF146         Pos. 2
                                                 +30°  -30°
                                    Pos. 4
   13
                                            Pos. 3





                                        Pos. 1        Pos. 1 ± 30°
                                                                      Pos. 1


                                             Pos. 5
                                    Direct-on-line                   Direct-on-line
                                    MCCB + AF                        MCCB + AF + OL