13/38            ABB  MOTOR PROTECTION AND CONTROL

          —

          DOL and reversing starters protected by overload relays
          With AF contactors - Open type version in kit form




                                    Application
                                    Full voltage direct-on-line and reversing starting for controlling three-phase asynchronous
                                    motors is a simple and economic solution characterised by a high starting torque (1.9 to 2.1
                                    times full-speed torque) and a starting current 5.5 to 7 times nominal current.
                                    I /In  C /Cn
                                    7
                    1SBC100058V0014  6 5        I


                                                              C = torque
                                    4                         I = current
          AF09-30-10 + TF42         3                         In = nominal current
                                                              Cn = nominal torque
                                    2
                                            C
                                    1
                                    0  10  30    60  80  100

                                    Coordination Types
                                    The contactor, the short-circuit protection device and the thermal overload relay control and
                                    protect motors against overload and short-circuits according to coordination types 1 and 2
                                    (IEC 60947-4-1 / EN 60947-4-1) defining the anticipated level of service continuity as follow:
                                    Type 1:  In short-circuit conditions, the contactor or starter does not endanger persons or in-
                        1SFC101153V0001   stallations and will not be able to then operate without being repaired or having
                                          parts replaced.
                                    Type 2:  In short-circuit conditions, the contactor or starter does not endanger persons or in-
          AF140-30-11 + TF140DU           stallations and will be able to operate afterwards. The risk of contacts light welding
                                          is acceptable.

                                    Main Technical Data
                                    Standards                      IEC 60947-4-1 / EN 60947-4-1
                                    Rated operational voltage Ue max.  690 V - 50/60 Hz
                                    Rated insulation voltage Ui
                                      acc. to IEC 60947-4-1        690 V
                                      acc. to UL / CSA             600 V
                                    Ambient air temperature
                                      Close to the device          ≤ 60 °C (TF42: 38 A above ≤ 50 °C)
                          1SBC100059V0014  Switching frequency     Refer to "Switching frequency diagrams" page
                                                                   IP20
                                    Degree of protection


          AF09-30-10 + BER16-4 + VEM4
          + TF42



   13





                                    Mounting positions
                                 1SFC101152V0001





          AF140-30-11 + BER140-4 + VM19 +
          TF140DU
                                     Pos. 1               Pos. 1
                                    Direct-on-line       Reversing