Direct-on-line starters protected by thermal overload relays
With AF contactors - Open type version in kit form
Contactors Thermal overload relays Accessories
IEC Control voltage Type Order code Setting ranges Type Order code
AC-3, 400 V Uc min. ... Uc max.
Rated Rated (1)
power current
kW A V 50/60 Hz V DC (2) A
4 8.5 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 7.60...10.0 TF42-10 1SAZ711201R1043
100...250 100...250 AF09-30-10-13 1SBL137001R1310
5.5 11.5 24...60 20...60 AF12Z-30-10-21 1SBL156001R2110 10.0...13.0 TF42-13 1SAZ711201R1045
100...250 100...250 AF12-30-10-13 1SBL157001R1310
7.5 15.5 24...60 20...60 AF16Z-30-10-21 1SBL176001R2110 13.0...16.0 TF42-16 1SAZ711201R1047
100...250 100...250 AF16-30-10-13 1SBL177001R1310
11 22 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 20.0...24.0 TF42-24 1SAZ711201R1051
100...250 100...250 AF26-30-00-13 1SBL237001R1300
15 29 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 29.0...35.0 TF42-35 1SAZ711201R1053
100...250 100...250 AF30-30-00-13 1SBL277001R1300
18.5 35 24...60 20...60 AF38Z-30-00-21 1SBL296001R2100 35.0...38.0/40.0 TF42-38 1SAZ711201R1055
100...250 100...250 AF38-30-00-13 1SBL297001R1300
18.5 35 24...60 20...60 AF40-30-00-11 1SBL347001R1100 30.0...40.0 TF65-40 1SAZ811201R1003
100...250 100...250 AF40-30-00-13 1SBL347001R1300
22 41 24…60 20…60 AF52-30-00-11 1SBL367001R1100 36.00…47.0 TF65-47 1SAZ811201R1004
100-250 100-250 AF52-30-00-13 1SBL367001R1300
30 55 24…60 20…60 AF65-30-00-11 1SBL387001R1100 50.0…60.0 TF65-60 1SAZ811201R1006
100-250 100-250 AF65-30-00-13 1SBL387001R1300
37 66 24…60 20…60 AF80-30-00-11 1SBL397001R1100 57.0…68.0 TF96-68 1SAZ911201R1003
100-250 100-250 AF80-30-00-13 1SBL397001R1300
45 80 24…60 20…60 AF96-30-00-11 1SBL407001R1100 75.0..87.0 TF96-87 1SAZ911201R1005
100-250 100-250 AF96-30-00-13 1SBL407001R1300
55 97 24…60 20…60 AF116-30-11-11 1SFL427001R1111 80…110 TF140DU-110 1SAZ431201R1002
100-250 100-250 AF116-30-11-13 1SFL427001R1311
75 132 24…60 20…60 AF140-30-11-11 1SFL447001R1111 100…135 TF140DU-135 1SAZ431201R1003
100-250 100-250 AF140-30-11-13 1SFL447001R1311
90 160 24…60 20…60 AF190-30-11-11 1SFL487002R1111 130…175 TA200DU-175 1SAZ411201R1005
100-250 100-250 AF190-30-11-13 1SFL487002R1311
110 195 24…60 20…60 AF205-30-11-11 1SFL527002R1111 150…200 TA200DU-200 1SAZ411201R1006
100-250 100-250 AF205-30-11-13 1SFL527002R1311
(1) For other control voltages, see "Voltage code table".
Note : for rated power above 110 kW, refer to "Starters protected by electronic overload relays".
(2) AF ... -11 not suitable for direct control by PLC-output.