          Climatic withstand of devices






          The life time of devices are mainly influenced by series of climatic factors which cause their corrosion.
          In practice, besides climatic conditions, there are other factors which may damage equipment such as fungi, insects (termites),
          dust, work site dirt and aggressive environment (salty or sulphurous atmosphere, etc.) which can often only be identified at the
          place of installation.
          Climatic stress, definitions and test conditions are dealt with in national publications such as the  DIN 50 series and UTE 63-100
          publication which are attached to international publications such as IEC 60068.
          The test conditions are:
          Description    Symbolization    Time of one cycle  Cycle phase time  Temperature     Relative humidity
                                                                             in test chamber
          Humidity       IEC 60068-2-30   24 hours          12 hours including   40 °C         95 %
          and            Test Db                            rise in temperature
          variable                                          12 hours including   25 °C         95 %
          temperature                                       cooling (open device)

          ABB contactors have been used for many years in the most countries, with hot and humid climates for example: Brazil, Indonesia,
          India or on ships. Experience has shown that ABB devices can be used in most countries throughout the world.
          The climate of the country in which the apparatus is installed is not the determining choice factor.

          Account must be taken of:
          •  the immediate environment of the devices (sheltered, ventilated, temperature),
          •  the aggressivity of the immediate atmosphere at the place of installation,
          •  the length and frequency of non operating periods.

          In the case of frequent condensation (i.e. the formation of condensation caused by rapid changes in temperature), heating resistors
          must be installed in cubicles (100 to 250 W per m³ of enclosure).
          The table below gives the cases where heating is necessary.
          Environment                        Operating conditions   Climate               Internal heating
                                                                                          of enclosure
          Inside         No running water    Continuous or not      All climates          Without
          premises       no condensation
                         With running water  Continuous             All climates          Without
                                             Frequent or long stops  Temperate            Without
                                                                    Tropical              With
          Outside, sheltered  No running water  Continuous or not   Temperate             Without
                         no condensation                            Tropical              With
          Outside or     With running water  Continuous             All climates          Without
          by the seaside                     Frequent or long stops  Temperate            Without
                                                                    Tropical              With
          The entrance of dust, insects, dirt, etc. in devices may be prevented if the appropriate degree of protection according to IEC 60529 is chosen (See "Degree of protection" table).