ABB  MOTOR CONTROL AND PROTECTION FOR ROLLING STOCK APPLICATIONS                  8/3

          —

          Customer assembled motor starting solutions






          ABB Expertise                                       Website access:
          ABB has acquired years of experience with respect to problems   https://www.lowvoltage-tools.abb.com/soc
          of coordination and is able to make a complete offer based on
          tests performed in its qualified laboratories. This offer covers   How to combine assemble and wire starter components
          400 V AC, 500 V AC, 690 V AC networks.              The section "customer assembled motor stating solutions" in
          A complete database of coordination tables, according to   this catalog gives the components lists and wiring diagrams to
          IEC 60947-4-1 (EN 60947-4-1), and UL 60947-4-1 between the   assemble the most typical motor starting solutions.
          branch circuit protective device and the motor starter is avail-  It covers direct-on-line Starters, reversing starters or star-delta
          able on the ABB Website.                            starters protected with manual motor starters or with thermal
          In the coordination tables the following short-circuit protection   overload relays for Type I or type II coordination for normal
          devices are recommended:                            starting time.
          •  Case circuit-breakers (MCCBs)                    Note:
          •  Miniature circuit-breakers (MCBs)                In order to confirm your starter combination ratings according
          •  Switch-disconnector-fuses (aM, gG and BS)        to ABB's lattest coordination test results, or to see other
          •  Manual motor starters (MMS).                       coordination of components please refer to the above
                                                                mentioned SOC tool. SOC tool get constant updates and
                                                                additions
          Select Optimized Coordination tool (SOC)
          Selected Optimized Coordination is a web tool for the selection   General remarks applicable to all tables
          of ABB products to be used in the following applications:
          •  Motor starting and protection                    •  Each table is defined for a maximum ambient temperature
          •  Selectivity between protection devices            of 40 °C. For higher temperatures, apply a derating factor
                                                                 according to the following rules:
          •  Back-up protection                               •  Fuses: factor of 0.8 applied to In for an ambient temperature
          •  Other devices protection.                         of 70 °C
                                                              •  MCCBs and MCBs: factor of 0.8 applied to In for an ambient
          In order to guarantee the best performance and the longest   temperature of 60 °C
          lifetime, devices involved into the applications mentioned   •  The starter derating factor depends on the operating
          above (short-circuit protection devices, contactors, overload     conditions of thermal overload relays:
          relays, softstarters, …) need to be coordinated.    •  Factor of 0.9 applied to In for an ambient temperature of 70 °C.
          •  The coordination among devices cannot be determined   •  Each table is defined for motor currents: 3-phase motors,
           directly: tests in power laboratories shall be carried out to   4-pole
           qualify the coordination type at low fault and high fault   •   Normal starting means a starting time < 2 s. - Difficult
           currents, according to IEC or UL standards.           starting means an accelerating time 10 s < ts < 30 s
          •  ABB coordination tables are the results of such tests and   •  Tripping classes of thermal overload relays according to
           represent the ABB offerings in terms of motor starting and   IEC 60947-4-1 (EN 60947-4-1): 10A and 10
           protection, selectivity, back-up and switch-disconnector   •  Tripping classes of electronic overload relays according to
           protection.                                         IEC 60947-4-1 (EN 60947-4-1): 10E, 20E, 30E selectable
          •  In Selected Optimized Coordination all available ABB   •  In the tables with MCCBs, these are fitted with the magnetic
           coordination tables are stored and easily accessible.  relay alone. Setting is always carried out at > 12.3 Ie AC-3 so
                                                               that the transient current peak occurring during starting does
                                                               not lead to  tripping.