8/4              ABB  MOTOR CONTROL AND PROTECTION FOR ROLLING STOCK APPLICATIONS

          —

          DOL and reversing starters protected by manual motor starters
          With AF..B contactors - open type version in kit form




                                    Application
                                    Full voltage direct-on-line (DOL) starting and reversing starting for controlling three-phase
                                    asynchronous motors is a simple and economic solution characterised by a high starting torque
                            I >
                                    (1.9 to 2.1 times full-speed torque) and a starting current 5.5 to 7 times nominal current.
                                    I  C
                                    /In  /Cn
                                    7
                                    6
                                                I
                                    5
                                                              I = current
                                    4                         C = torque
                                                              In = nominal current
                                    3
                                                              Cn = nominal torque
                                    2
                                            C
                                    1
                        1SBC101546V0014  0  10  30  60  80  100

                                    The contactor and the manual motor starter control and protect motors against overload and
          DOL starter               Coordination types
          MS132-10B + BEA16-4       short-circuits according to coordination types 1 and 2 (IEC 60947-4-1 / EN 60947-4-1) defining
          + AF09ZB-30-10            the anticipated level of service continuity as follow:
                                    Type 1: In short-circuit conditions, the contactor or starter does not endanger persons or
                                    installations and will not be able to then operate without being repaired or having parts
                                    replaced.
                                    Type 2: In short-circuit conditions, the contactor or starter does not endanger persons or
                                    installations and will be able to operate afterwards. The risk of contacts light welding is
                                    acceptable.
                             I >
                                    Main Technical Data
                                    Standards                     IEC 60947-4-1 / EN 60947-4-1, IEC 60947-2 / EN 60947-2
                                                                  IEC 60947-5-1 / EN 60947-5-1
                                                                  IEC 61373 Category 1 Class B
                                                                  Applicable parts of IEC 60077-1/2 and EN 50155
                                    Rated operational voltage Ue max.  690 V - 50/60 Hz
                                    Rated insulation voltage Ui
                                      acc. to IEC 60947-4-1       690 V
                                      acc. to UL / CSA            600 V
                                    Switching frequency           ≤ 15 starts/hour - 80 % max. load factor - with max. 1.5 s starting time
                               1SBC101547V0014  Ambient air temperature  use with MS132-B ≤ 60 °C
                                                                  ≤ 30 starts/hour - 50 % max. load factor - with max. 1.5 s starting time
                                      Close to the device
                                    Degree of protection
                                    Fixing                        IP20
                                      On rail acc. to  Manual motor starter on 35 x 7.5 mm or 35 x 15 mm rail
          Reversing starter
          MS132-10B + BEA16-4 + BER16-4   IEC 60715, EN 60715  Contactor fitted with BEA-..4 connecting link and fixed by:
          + VEM4 + AF09ZB-30-10
                                                                  - 2 x M4 screws on the bottom side for direct-on-line starter 1 direction
                                                                  - 2 x M4 screws place diagonally for reversing starter
                                                                  Note: the difference of depth between manual motor starter and contactors must
                                                                  be compensated with the use of washers or spacers (not supplied)
                                      By screws      Manual motor starter fitted with 2 screw fixing kits FS116 by 2 x M4 screws on the top side
                                      (not supplied)
   08
                                                           Contactor fitted with BEA-..4 connecting link and fixed by :
                                                                  - 2 x M4 screws on the bottom side for direct-on-line starter 1 direction
                                                                  - 2 x M4 screws place diagonally for reversing starter
                                    Mounting positions








                                                                                                                  1SBC100248S0201
                                    Pos. 1    Pos. 5                     Pos. 1
                                                                                  Pos. 5
                                    DOL starters                       Reversing starters