ABB  MOTOR CONTROL AND PROTECTION FOR ROLLING STOCK APPLICATIONS                 8/17

          —

          DOL and reversing starters protected by overload relays
          With AF..B contactors - Open type version in kit form
          Switching frequency diagrams


          General
          Overload relays cannot be operated at any arbitrary switching frequency in order to avoid tripping. Applications involving up to
          15 operations per hour are acceptable. Higher switching frequencies are permitted if the duty ratio and the motor starting time are
          allowed for and if the motor's making current does not appreciably exceed 6 times the rated operating current. Please refer to the
          adjacent diagram for guideline values for the permitted switching frequency.





          Thermal overload relay
          Intermittent periodic duty  Example:

             (Op/h)
          Switching frequency (ops/h)  switching frequency  120  t   = 1.5 s  a  Starting time of the motor: 1 second - Duty ratio: 40 % means a permitted
             140
                                    switching frequency of max. 60 operating cycles per hour.
             100
              80
                       t   = 0.5 s
                    a
              60
                  a
                    t   = 1 s
              40
                 a
              20
                 a
                 t   = 5 s
              0  t   = 3 s
               0  20  40  60  80  100  (%)
                   duty ratio
                    Duty ratio (%)
              ta: motor starting time