Page 5 - DEHN-protects-photovoltaic-systems
P. 5

Buildings with PV installations                                                                                            A        Main distribution board                                                      Part No.

                                                                                                                                                                                                                            941 306
                                                                                                                                                        DEHNshield    Basic (depending on the system configuration)          (TNC)
            Without external lighting protection                                                                                                        The combined arrester is mounted directly at the entrance point into the building.    941 406
                                                                                                                                                        It protects the electrical installations in the immediate vicinity.  (TNS)
                                                                                                                                                                                                                            941 316
                                                                                                                                                                                                                             (TT)
                                                                                                                                                        alternatively: DEHNguard    modular (depending on the system configuration)  952 400
                                                                                                                                                        This surge arrester protects against overvoltages from inductive couplings by distant lightning    (TNS)
                                                                                                                                                        strikes and from switching overvoltages. It must be installed downstream of the electricity meter   952 381
                                                                                                                                                        which means that it does not protect the Smart Meter and Smart Meter Gateway.  (TT)
                                                          C2                                                                            B        Internet / telephone / broadband                                          Part No.

                                                                                                                                                        DEHNbox TC180
                                                          E                                                                                             The combined arrester offers protection in the event of lightning strikes and overvoltages.
                                                                                                                                                        It secures telephone and DSL connections. Its compact design makes it quick to install in    922 210
                                                                                                                                                        new buildings and easy to retrofit in existing buildings.
                                                                                                                                        C        PV installation                                                            Part No.

                                                                                                                                                        DEHNguard M YPV                                                     952 565
                                                                                                                                                        This type 2 arrester is specially designed for application in PV systems and protects    (1170 V)
                                                                                                                                                        the DC side of the inverter against surges from inductive couplings. If there is more
                                                                                                                                                        than 10 metres of cable between the PV system and the inverter, a further arrester    952 567
                                                                                                                                                        is necessary in the roof area.                                      (1500 V)

                                                                                                                                                        alternatively: DEHNcube YPV SCI 1000
                                                                                                                                                        Type 2 arrester DEHNcube YPV SCI provides comprehensive protection for a PV system in    900 910
                                                                                                                                                                                                                            (1 MPPT)
                                                                                                                                                        an enclosure. It is mounted directly upstream of the inverter and is available in two versions,
                                                                                                                                                        1 MPPT and 2 MPPT. If there is more than 10 metres of cable between the PV system and    900 920
                                                                                                                                                        the inverter, a further arrester is necessary in the roof area.     (2 MPPT)
                     A                                                                                                                 D        AC side inverter                                                            Part No.
                     B
                                                        C1                                                                                              DEHNguard    M TNS or DEHNguard M TT
                                                        D                                                                                               The surge arrester protects against overvoltages from inductive couplings by distant    952 405
                                                                                                                                                                                                                             (TNS)
                                                                                                                                                        lightning strikes and from switching overvoltages.  If there is more than 10 metres of
                                                                                                                                                        cable between the service entrance box and the inverter, a further type 2 surge arrester    952 315
                                                                                                                                                        is required at the inverter.                                         (TT)
                                                                                                                                        E        Equipotential bonding                                                      Part No.

                                                                                                                                                        UNI earthing clamps/saddle clamps
                                                                                                                                                        The clamps are suitable for integrating the mounting systems of PV installations    540 250
                                                                                                                                                        in the functional equipotential bonding / the functional earthing or the
                                                                                                                                                        lightning equipotential bonding.                                    365 250
            Surge protective devices should be installed even
            if there is no external lightning protection system.

            The standards IEC 60364-7-712 and IEC 61643-32 describe   The same applies to battery storage systems; If the storage
            type 2 arresters as protective devices. DEHN recommends   system is in the immediate proximity (less than 10 m) of
            type 1 arresters because these protective devices can be    the surge protective device, no further protective devices
            installed upstream of the meter and offer additional    are required.
            protection against partial lightning currents. This provides
            optimum protection for devices such as smart meters.
            It is necessary to protect both the electrical components on
            the AC and DC side and any data interfaces. The protective
            devices should be installed as closely as possible to the
            device to be protected, e.g., inverter. If the line between the
            surge protective device and, e.g., the inverter is longer than
            10 metres, an additional type 2 surge protective device is
            required.
                                                                                                                                      Further info on the topic of lightning and surge protection
                                                                                                                                      for modern residential buildings can be found on our website.

                                                                                                                                       www.de.hn/pvrb

                                                                                                                                      We are here to support you with any technical queries:
                                                                                                                                      Team Support
                                                                                                                                      Telephone: +49 9181 906 1750
                                                                                                                                      E-Mail: [email protected]



     8                                                                                                                                                                                                                                    9
   1   2   3   4   5   6   7   8   9   10