Smoke / heat extraction systems, fire alarm systems,

            voice alarm systems




            Technical fire protection equipment and especially fire alarm   material losses but, above all, consequential damage such as
            systems are of vital importance. They enable modern   production downtime, loss of data or the appointment of a
            buildings with elaborate architecture and both a complex   fire watch should the fire alarm system fail.
            infrastructure and purpose to easily meet today’s fire   Coordinated lightning and surge protection according to of
            protection and safety requirements.                                                                                      Surge protection                                 Application / interface  Type          Part No.
                                                              IEC 62305-4 prevents false alarms or destruction resulting
            The systems are used for fire detection, alarming and   from atmospheric discharges or switching overvoltages at         Smoke / heat extraction system
            evacuation and thus serve the protection of people and   the corresponding transitions of the relevant lightning                         DEHNpatch Class E                LAN connection to building   DPA M CLE RJ45B 48 929 121
            material assets. A further critical task as a superordinate   protection zone and increases system availability.                         Universal arrester for Industrial Ethernet,   services management system
            system element is to take over the central function of the   Additional shielding and earthing measures for hazard alarm                 PoE+.
            control systems of other safety-related systems and equip-  systems should be taken in accordance with the VdS  2833
                                                                                                      1)
            ment in the event of fire.                                                                                                               DEHNguard M TT 2P                Power supply smoke     DG M TT 2P 275  952 110
                                                              guideline (see also DIN VDE 0845 - appendix 1). Moreover, it
            Lightning strikes and voltage surges can cause irreparable   should be checked whether additional surge arresters are                    Modular surge arrester for single-phase TT   extraction system
                                                                                                                                                     and TN systems.
            damage to electrical and electronic equipment that is not   required due to the indicators listed in the VdS 2833
            adequately protected. In addition to electrical consumers   guidelines. If this is the case, the operator of the hazard
            and telecommunications equipment, this applies to safety   alarm system must be informed of the necessity for protec-                    BLITZDUCTORconnect               Actuator, air intake dampers,  BCO ML2 BD 24  927 244
            systems such as fire alarms, voice alarms or heat/smoke   tion measures.                                                                 Space-saving, modular combined arrester   alarms
            extraction systems. The damage not only includes purely                                                                                  with a width of 6 mm and push-in connec-
                                                                                                                                                     tion technology.
                                                                                                                                                     BLITZDUCTOR XT                   Actuator air intake dampers   BXT ML4 BE 36   920 336
                                                                                                                                                     Combined arrester with RFID LifeCheck for   (24 V DC/AC; 5 W)  BXT BAS  920 300
                                                                                                                                                     protecting 4 single lines sharing a common              (Application up to
                                                                                                                                                     reference potential.                                    max. 1.8 A)
                        230 V                     230 V                               230 V
                   SDB                       SDB                TE                SDB          MP      M                                             or
                       < 10 m                    < 10 m                telecoms       < 10 m
                                          distribution board                                                                                         DEHNguard S                                             or                   or
                                                                                                                                                     Universal surge arrester                                DG S 48 FM      952 098
               BMS                   alarm FACP                FBKD
                         SHES                      FACP                                 VAS                                          Fire alarm system
                                                                   alarming areas 1..n
                                                                                                                                                     DEHNguard M TN                   Power supply           DG M TN 275     952 200
                                                                                                                                                     Modular surge arrester for single-phase TN   alarm panel 230 V
                                                                                                                                                     systems.
                  smoke suction                          NAD       NAD
                   system
                                                                                                                                                     BLITZDUCTOR XT                   Ring bus fire alarm system  BXT ML4 BE 24  920 324
                                           FBIOS         combination   SD                LS         LS                                               Combined arrester with RFID LifeCheck for               BXT BAS         920 300
                                                         OSD/AST
                                                                                                                                                     protecting 4 single lines sharing a common
                    ventilation button                                                                                                               reference potential.
                            M                 AST                      SD                LS         LS                                               DEHNrail                         Alarm contact e.g. to lift con-  DR M 2P 255  953 200
                                                                                                                                                     Two-pole surge arrester consisting of a base   trol, ventilation, sprinkler
                          domelight                                                                                                                  part and plug-in protection module.
                                                       line coupler  line coupler
                                              OST        C         C
                                                         EX        EX                                                                                BLITZDUCTOR XT or -VT            Conductor key depot    BXT ML2 BD S 24  920 244
                            rain / weather                                                                                                           Space-saving, modular combined arrester                 BXT BAS         920 300
                              sensor                                                          external loudspeaker                                   with a width of 6 mm and push-in connec-                or                   or
                                                         sprinkler  lift                                                                             tion technology.                 Heating                BVT ALD         918 408
            BMS:  Building management system  AST:   Acoustic signal transmitter   LS:   Loudspeaker                                                 BLITZDUCTOR XT                   Telecommunication      BXT ML4 B 180   920 310
            SDB:  Sub distribution board   FACP:  Fire Alarm Control Panel      MP:   Micro phone                                                    Space-saving four-pole lightning current   connection   BXT BAS         920 300
            SHES:  Smoke and heat extraction system  FBIOS:  Fire brigade information / operating system  VAS:  Voice alarm system                   arrester with RFID LifeCheck for almost all
                                         FBKD:  Fire brigade key depot                                                                               applications.
                                         NAD:  Not automatic detector
                                         OST:  Optical signal transmitter
                                         OSD:  Optical smoke detector                                                                Public address systems - voice alarm
                                         SD:   Smoke detector                                                                                        DEHNvario                        Public address systems -   DVR 2 BY S 150 FM  928 430
                                         TE:   Telecoms
                                                                                                                                                     Combined arrester for protecting electro-  line loudspeaker
                                                                                                                                                     acoustic systems.