Page 4 - DEHN-protects-technical-building-equipment
P. 4

Risk assessment                                                                                                        Lightning protection zone concept

            A lightning protection risk analysis allows you to assess and determine the risk                                       In case of the lightning protection zone concept, the building is divided into zones

            potential for structures. This risk analysis forms the basis for minimising risks and                                  with different risk potential. Inner and outer lightning protection zones are defi-
            defining economically optimal protection measures – Tailored to the existing                                           ned depending on the lightning threat. Based on these zones, it is determined
            structures and their use.                                                                                              where which measures are required.

                                                                                                                                   Modern structures and buildings are becoming smart. They   to surges caused by lightning discharge. The principle of
                                                                                                                                   are based on a variety of networked technical components:   lightning protection zones (LPZ) according to IEC 62305-4
            Predictive risk management involves calculating risks for the   Lightning protection risk analyses aim to objectify and   Building management, telecommunication, control and   describes effective protection against surges caused by light-
            company. It provides the basis for decisions to limit these   quantify the risk posed by direct and indirect lightning   security systems to name but a few. Failure of individual   ning electromagnetic impulse (LEMP).
            risks and shows which risks should reasonably be covered by   strikes to structures and their contents.                technical building equipment components can have
            insurance.                                                                                                             far-reaching consequences and even bring the entire   According to this principle, the structure to be protected
                                                                                                                                   building to a standstill.                         should be divided into inner lightning protection zones of
                                                              The risk analysis specified in IEC 62305-2 ensures that a                                                              different LEMP threat values. Suitable LPZ can be defined
            The risk of lightning strikes must also be specifically   lightning protection concept can be drawn up that is         Although external lightning protection protects people and   depending on the number, type and sensitivity of the
            considered for companies using extensive electronic   comprehensible to all parties involved and technically and       material assets in buildings from the risk of fire, it does not   electronic devices / systems.
            equipment for production or providing services. It should be   economically optimised, i.e. can ensure the protection   protect the electrical and electronic systems from failure due
            noted that losses incurred due to the lack of availability of   required at the lowest possible cost. The protection
            electronic systems and, as a result, production or services,   measures resulting from the risk analysis are described in   Outer zones:                                 Inner zones:
            coupled with the potential loss of data often by far exceed   detail in parts 3 and 4 of the IEC 62305 series.
            the physical damage to the hardware of the relevant system.                                                            LPZ 0A: Zone where the threat is due to direct lightning   Inner zones are protected against direct lightning strikes.
                                                                                                                                   strikes and the unattenuated lightning electromagnetic field.   They are divided into:
                                                                                                                                   The systems affected, such as lines extending beyond   LPZ 1: Zone where impulse currents are limited by current
                                                                                                                                   buildings, may be subjected to the full lightning current.  sharing and surge protective devices at the zone boundaries.
            Procedure:                                                                                                             LPZ 0B: Zone protected against direct lightning strikes, but   Spatial shielding may attenuate the lightning electromagnetic
            Assessment of the structure                       Definition of protection measures                                    where the threat is the unattenuated lightning electromag-  field. Ring lines with detectors are often installed in LPZ 1.
                                                                                                                                   netic field. The systems affected, such as alarm lights or
            In a first step, the building is assessed based on its equip-  The protection measures are defined based on the determi-  sirens, may be subjected to partial lightning currents.  LPZ 2-n: Zone which, compared to LPZ 1, is additionally
            ment, location and risk potential. The result of this assess-  ned risk. These include, for example various equipotential                                                protected against impulse currents and the lightning
            ment is a so-called risk R / whether the determined risk   bonding measures or definition of a class of LPS (LPL,                                                        electromagnetic field and is therefore subject to less
            exceeds a tolerable value Rt. The figures below show a simp-  Lightning Protection Level) and thus external lightning                                                    interference.
            lified representation of the relationship between the type of   protection measures. The aim is to reduce the risk to an
            damage, source of damage and type of loss and provide an   acceptable level. After that, internal lightning protection
            initial overview of the risk potential.           measures (surge protection) are then taken. These are based                                                                                           FCP:  Fire control panel
                                                              on the so-called lightning protection zone concept.                                                                                                   FBKD: Fire brigade key depot
                                                                                                                                                                                                                    FBIOS: Fire brigade information
                                                                                                                                                                                                                      and operating system
                                                                                                                                                         M                                                          LV /   Low voltage / main
                                                                                                                                                                                                                    MDB:  distribution board
                                                                                                                                                             M
                                                                                                                                                                                                                    SDB:  Sub distribution board
                   Risks                                                                         Risks
                                                                                                                                                   SDB


                Fire                                                                          Fire                                  charging                               FBIOS
                                                                                                                                    post                       SDB  medical
                                                                                                                                                                    device
                                                                                                                                                                                 FBKD
                                                                                                                                            server
                      Human                                                                         Human
                  Surges                                                                         Surges
                                                                                                                                                 LV / MDB
             Source of damage S1: Lightning strike to a structure  Source of damage S3: Lightning strike to an incoming supply line                                     FCP


                                                                                                                                                                                                                       Simplified diagram
                  Risks                                                                          Risks

                                                                                                                                                    Experience has shown that hospitals are designed according to class of LPS 2. This includes a defined
                                                                                                                                                    risk as well as the necessary external lightning protection, equipotential bonding and surge protection
                  Surges                                                                        Surges                                              measures. In addition to risk management, statutory and normative regulations such as the relevant
                                                                                                                                                    building regulations, IEC (or EN) specifications or fire protection requirements must also be observed
             Source of damage S2: Lightning strike near a structure  Source of damage S4: Lightning strike near an incoming supply line             for hospitals.



      4                                                                                                                                                                                                                                  5
   1   2   3   4   5   6   7   8   9