Page 9 - DEHN-protects-technical-building-equipment
P. 9

Lightning equipotential protection bonding /

 surge protection


 Consistent lightning equipotential bonding is an important basis for the safe func-
 tioning of the entire lightning protection system. For an effective surge protection   3
 concept, it is important to ensure that the three-stage protection principle is ob-
 served.



 The consequences of a lightning strike are particularly   Three-stage protection principle
 serious in buildings designed in accordance with Industry   In addition to taking the different lightning protection zones   2  5
 4.0, in systems for renewable energy generation or in   into account, an effective surge protection concept is also
 systems with a modern building infrastructure. It is not only   based on three protection stages, in which the incoming   4
 a matter of destroying valuable system technology, but also   energy is gradually reduced to a low level that is safe for   1
 of damage resulting from the interruption of operations   terminal devices:   6  7
 such as failure of work processes, IT systems and manufac-                                                     6   7
 turing systems. An important basis for the necessary system   ƒ Stage 1: Type 1 lightning current arresters / combined  5  7
 availability of such modern building equipment as well as for   arresters at the entrance point into the building (lightning
 the safe functioning of the entire lightning protection   equipotential bonding).
 system is a consistent lightning equipotential bonding for all   ƒ Stage 2: Type 2 surge arresters usually installed in the
 electrical cables entering the building from outside.
 downstream sub-distribution boards.  Lightning equipotential bonding / surge potection  Application / interface  Type  Part No.
 Lightning equipotential bonding (according to IEC 62305-3)   ƒ Stage 3: Type 3 surge arresters, which can be installed
 is an extension of protective equipotential bonding accor-  directly at the terminal device or in socket outlets.  1  DEHNvenCI 1 255 FM  Power supply line  DVCI 1 255 FM  961 205
 ding to IEC 60364-4-41. In addition to all those extraneous   Spark-gap-based combined arrester   230 / 400 V
                                  with integrated lightning current
 conductive parts which are directly connected to the   Interaction of the individual protection stages ensures the   arrester backup fuse.
 equipotential bonding, the lightning equipotential bonding   best possible protective effect. To this end, the relevant
 must also encompass the supply lines of the network   arresters must be energy coordinated according to
 operator, communication lines and other electrical interfaces   IEC 60364-5-53 clause 534.
 and systems which inject lightning currents into the   2  LSA-plus technology  Telecommunication line  DRL 10 B 180 FSD  907 401
 building. The connection must be made as closely as   Modular system of lightning current   EF 10 DRL  907 498
                                  and surge arresters, can be combined
 possible to the entrance point into the building by way of   to a single combined arrester.  DRL PD 180  907 430
 type 1 lightning current arresters.
             3                    DEHNgate                     SAT system / radio-relay   DGA GFF TV  909 705
                                  The DEHNgate GFF TV combined arres-  system / BOS (emergency
                                  ter protects the SAT system / radio-relay   service) radio
                                  antenna at the entrance point into the
 Type 1   Type 2   Type 3         building.
 lightning current arrester  surge arrester  surge arrester
             4                    High-performance isolating spark   Gas network      TFS             923 023
                                  gap
                                  For indirect connection/earthing of
 Sub-distribution board           functionally isolated system parts.
 Main distribution board  terminal device  Terminal device
             5                    DEHNshield TNS               AC-supplied charging post or   DSH TNS 255  941 400
                                  Allows compact lightning equipotential   outdoor lighting system
                                  bonding including protection of termi-  230 / 400 V
                                  nal devices.                 Supply line


             6                    DEHNshield TN                Power supply toll barrier  DSH TN 255  941 200
                                  Prewired, application-optimised
                                  combined arrester for single-phase TN
                                  systems.

             7                    BLITZDUCTORconnect           Data and communication line  BCO ML2 BD 24  927 244
                                  Space-saving, modular combined arres-
                                                               Charging post or toll barrier
 6/4 kV  4/2.5 kV   ≤ 1.5 kV      ter with a width of 6 mm and push-in
                                  connection technology.
 Example of a three-stage protection concept



      More information at:       Use our online configurators
      de.hn/configurators        for easy and fast selection



 8                                                                                                                9
   4   5   6   7   8   9   10   11   12   13   14