Page 1100 - Din prodcuts 2020
P. 1100
10/178 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
Connector units
with mechanical interlock, CUMI
To ensure maximum safety for users, we can offer special connector
units.
Technical data Unit C-Line B-Line
Norminal current A 200 250 250 400
Rated current A 250 285 315 450
Rated voltage V 1000 1000
Rated frequency Hz 50/60 50/60
Withstand voltage (1 Min/50 Hz) V 4000 4000
Protection grade IP55 IP55
10
Shock resistance IK07 IK07
Ambient temperature °C -40/+70 -40/+70
Insulation resistance (Phase-phase and MOhm >500 >500
phase-earth)
Comparative tracking index of the insert CTI >600 >600
Weight 4 poles (3L+PEN) kg 25.1 45.6
Weight 5 poles (3L+N+PE) kg 25.3 47.1
Connection bolts for cable shoes M8 M10
Max cross section pilot cable, mm 2 4 4
conductor (EN 60228 Class 1)
Diameter of cable - normal mm 20-70 20-70
other diameters on request