Page 180 - Din prodcuts 2020
P. 180

1/170            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201
  1



          —
          High performance MCBs
          S800U series technical features




                                                              S800U
          General Data
          Tripping characteristics                            K, Z
          Standards                                           UL489
          Poles                                               1 … 4
          Rated current I                         A           10...100
                    e
          Rated frequency f                       Hz          50/60
          Rated insulation voltage U  acc. to IEC/EN 60664-1  V  AC 690
                           i
          Rated impulse withstand voltage U   (1.2/50 µs)  kV  8
                                 imp.
          Overvoltage category                                IV
          Pollution degree                                    3
          Suitability for isolation                           yes
          Data acc. to IEC/EN 60947-2
          Rated operational voltage U  e          V           AC 240/415
          Min. operating voltage                  V           AC 12
          Rated ultimate short-circuit capacity I  kA         AC 240 V (1-pole) = 30 kA
                                   cu
                                                              AC 415 V (multipole) = 50 kA
          Rated service short-circuit capacity I  cs  kA      AC 240 V (1-pole) = 25 kA
                                                              AC 415 V (multipole) = 40 kA
          Reference temperature for tripping characteristics  °C   25 °C
          Electrical and Mechanical Endurance     ops.        10...32 A: 10000 electrical / 10000 mechanical
                                                              40...100 A: 6000 electrical / 10000 mechanical
          Data acc. to UL / CSA
          Rated voltage                           V           AC 240
          Rated interrupting capacity acc. to UL 1077  kA
          Short-circuit current rating acc. to UL 489  kA     AC 240 V (1-pole) = 30 kA
                                                              AC 240 V (multipole) = 50 kA
          Short-circuit current rating acc. to UL 489B  kA
          Reference temperature for tripping characteristics  25 °C
          Electrical and Mechanical endurance     ops.        acc. to UL489
                                                              6000 electrical; 4000 mechanical
          Mechanical Data
          Protection degree acc. to EN 60529                  IP20; IP40 (actuating end only)
          Shock resistance acc. to IEC/EN 60068-2-30          IEC 61373 Cat. 1 Class B, 5 g/30 ms acc. To IEC 60068-27 Test Ea
          Vibration resistance acc. to IEC/EN 60068-2-6       IEC 60068-2-6 Test Fc;
                                                              2 - 13.2 Hz/1 mm
                                                              13.2 - 100 Hz/0.7 g
                                                              with load 100 % x I e
          Environmental conditions (damp heat)    °C/RH       12 + 12 cycle with 55 °C/90 - 96 %
          acc. to IEC/EN 60068-2-30                           and 25 °C/95 - 100 %
          Environmental conditions (dry heat)     °C/RH       16 hours 55 °C/2 hours 70 °C
          acc. to IEC/EN 60068-2-2 Test B                     with damp heat 55 %
          Ambient temperature                     °C          -25 … +60
          Storage temperature                     °C          -40 … +70
          Installation
          Terminal                                            Failsafe cage or ringlug terminal
          Connections (top/bottom) – C  only      mm 2        1 … 50 stranded
                              u
                                                               1 … 70 flexible
                                                  AWG         10 - 30 A: 14 - 2 AWG
                                                              40 - 100 A: 1 - 8 AWG
          Tightening torque                       Nm          3.5
                                                  in-Ibs.     31
          Screwdriver                                         POZI 2
          Mounting                                            any
          Mounting position                                   any
          Supply                                              any
          Dimensions and weight
          Pole dimensions (H x L x W)             mm          95 x 26.5 x 82.5
          Pole weight                             g           240
   175   176   177   178   179   180   181   182   183   184   185