Page 182 - Din prodcuts 2020
P. 182
1/172 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
1
—
High performance MCBs
S804U-PVS series technical features
S804U-PVS
General Data
Tripping characteristics PVS
Standards UL489B (Photovoltaic)
Poles 4
Rated current I A 5
e
Rated frequency f Hz -
Rated insulation voltage U acc. to IEC/EN 60664-1 V DC 1500
i
Rated impulse withstand voltage U (1.2/50 µs) kV 8
imp.
Overvoltage category III
Pollution degree 2
Suitability for isolation yes
Data acc. to IEC/EN 60947-2
Rated operational voltage U e V -
Min. operating voltage V -
Rated ultimate short-circuit capacity I cu kA -
Rated service short-circuit capacity I cs kA -
Reference temperature for tripping characteristics °C -
Electrical and Mechanical Endurance ops. -
Data acc. to UL / CSA
Rated voltage V DC 1000
Rated interrupting capacity acc. to UL 1077 kA -
Short-circuit current rating acc. to UL 489 kA -
Short-circuit current rating acc. to UL 489B kA 3 kA
Reference temperature for tripping characteristics 50 °C
Electrical and Mechanical endurance ops. acc. to UL489
1000 electrical; 1000 mechanical
Mechanical Data
Protection degree acc. to EN 60529 IP20; IP40 (actuating end only)
Shock resistance acc. to IEC/EN 60068-2-30 -
Vibration resistance acc. to IEC/EN 60068-2-6 -
Environmental conditions (damp heat) °C/RH -
acc. to IEC/EN 60068-2-30
Environmental conditions (dry heat) °C/RH -
acc. to IEC/EN 60068-2-2 Test B
Ambient temperature °C -25 … +60
Storage temperature °C -40 … +70
Installation
Terminal Failsafe cage terminal
Connections (top/bottom) – C only mm 2 1 … 50 stranded
u
1 … 70 flexible
AWG 14 AWG - 2 AWG
Single conductor per terminal, 75C wire
Flexible Cross-section of conductors mm 2 -
(top/bottom) AWG 14 AWG - 2 AWG
Single conductor per terminal - copper only, 75C wire
Tightening torque Nm 3.5
in-Ibs. 31
Screwdriver POZI 2
Mounting any
Mounting position any
Supply any
Dimensions and weight
Pole dimensions (H x L x W) mm 142 x 26.5 x 82.5
Pole weight g 240