1/178            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201
  1



          —
          High performance MCBs
          S800PV-SP series technical features




                                                               S800PV-SP
          General Data
          Tripping characteristics                             SP
          Standards                                            IEC / EN 60947-2 and Annex P
          Poles                                                2 ... 4
          Rated frequency I e                      A           5 ... 125
          Rated frequency f                        Hz          -
          Rated insulation voltage U  acc. to IEC/EN 60664-1  V  DC 1500
                            i
          Rated impulse withstand voltage U imp.  (1.2/50 µs)  kV  8
          Overvoltage category                                 III*
          Pollution degree                                     2
          Suitability for isolation                            yes
          Data acc. to IEC/EN 60947-2
          Rated operational voltage U              V           2-pole
                             e
                                                               DC 800 V: 5 … 125 A
                                                               3-pole
                                                               DC 1200 V: 5 … 125 A
                                                               4-pole
                                                               DC 1500 V: 5 … 125 A
          Min. operating voltage                   V           -
          Rated ultimate short-circuit capacity I  cu  kA      5 … 16 A acc. IEC 60947-2 Annex P.
                                                               I  = 5 kA
                                                               cu
                                                               20 … 125 A, acc. IEC 60947-2, I  = 5 kA
                                                                                   cu
                                                               20 … 125 A, acc. IEC 60947-2 Annex P.
                                                               I  = 3 kA
                                                               cu
          Rated service short-circuit capacity I   kA          I  = I
                                   cs                          cu  cs
          Reference temperature for tripping characteristics  °C  40 °C
          Electrical and Mechanical Endurance      ops.        acc. to Annex P:
                                                               5 … 16 A: 300 electrical/9700 mechanical
                                                               acc. to IEC 60947-2 (general part):
                                                               20 … 100 A: 1500 electrical/8500 mechanical
                                                               125 A: 1000 electrical/9000 mechanical
          Mechanical Data
          Housing                                              Material group I, RAL 7035
          Toggle                                               black, lockable
          Classification acc. To NF F 126-101, NF F 16-102     -
          Protection degree acc. to EN 60529                   IP20; IP40 (actuating end only)
          Shock resistance acc. to IEC/EN 60068-2-30           IEC 61373 Cat. 1 Class B, 5 g / 30 ms acc. To IEC 60068-27 Test Ea
          Vibration resistance acc. to IEC/EN 60068-2-6        IEC 60068-2-6 Test Fc;
                                                               2 - 13.2 Hz/1 mm
                                                               13.2 - 100 Hz/0.7 g
                                                               with load 100 % x I e
          Environmental conditions (damp heat)     °C/RH       12 + 12 cycle with 55 °C/90 - 96 % and 25 °C/95 - 100 %
          acc. to IEC/EN 60068-2-30
          Environmental conditions (dry heat)      °C/RH       16 hours 55 °C/2 hours 70 °C with damp heat 55 %
          acc. to IEC/EN 60068-2-2 Test B
          Ambient temperature                      °C          -25 … +60
          Storage temperature                      °C          -40 … +70
          Installation
          Terminal                                             Failsafe cage or ringlug terminal
          Connections (top/bottom) - C  only       mm 2        1 … 50 stranded
                              u
                                                               1 … 70 flexible
          Tightening torque                        Nm          3.5
                                                   in-Ibs.     31
          Screwdriver                                          POZI 2
          Mounting                                             any
          Mounting position                                    any
          Supply                                               any
          Dimensions and weight
          Pole dimensions (H x L x W)              mm          95 x 26.5 x 82.5
          Pole weight                              g           240
          * The pollution degree of the product, as defined in standard IEC 60947-1, is related to its micro environment, to which equipment is exposed. It may be different from that of
          the macro-environment. According to where the equipment is located, the pollution degree of the macro environment can be considered up to category IV if protection is
          offered by means of such as an adequate enclosure or internal heating to prevent absorption or condensation of moisture.