High performance MCBs
S802PV-M-H and S800PV-SD technical features
S802PV-M-H S800PV-SD
General Data
Tripping characteristics none none
Standards IEC / EN 60947-3 IEC / EN 60947-3 and Annex D
Poles 2 (polarized) 2 ... 4
Rated current I A 32, 63, 100 32, 63, 125
e
Rated insulation voltage U acc. to IEC/EN 60664-1 V DC 1500 DC 1500
i
Rated impulse withstand voltage U imp. (1.2/50 µs) kV 8 8
Overvoltage category III* III*
Pollution degree 2 2
Suitability for isolation yes yes
Data acc. to IEC/EN 60947-3
Rated operational voltage U e V DC 1000 V: 2-pole DC 800V: 2-pole
DC 1200V: 3-Pole
DC 1500 V: 4-pole
Min. operating voltage V - -
Rated short-term withstand current I kA 1.5 1.5
cw
Rated short-circuit making capacity I cm kA 0.5 0.5
Utilisation category DC-21 A DC-21 A, DC-PV2
Electrical and Mechanical Endurance ops. 1500 electrical / 10000 mechanical 32, 63 A: 1500 electrical /
10000 mechanical
125 A: 1000 electrical /
8000 mechanical
Mechanical Data
Housing Material group I, RAL 7035 Material group I, RAL 7035
Toggle black, lockable black, lockable
Classification acc. To NF F 126-101, NF F 16-102 - -
Protection degree acc. to EN 60529 IP20; IP40 (actuating end only) IP20; IP40 (actuating end only)
Shock resistance acc. to IEC/EN 60068-2-30 IEC 61373 Cat. 1 Class B, 5 g / IEC 61373 Cat. 1 Class B, 5 g /
30 ms acc. To IEC 60068-27 Test Ea 30 ms acc. To IEC 60068-27 Test Ea
Vibration resistance acc. to IEC/EN 60068-2-6 IEC 60068-2-6 Test Fc; IEC 60068-2-6 Test Fc;
2 - 13.2 Hz/1 mm 2 - 13.2 Hz/1 mm
13.2 - 100 Hz/0.7 g 13.2 - 100 Hz/0.7 g
with load 100 % x I with load 100 % x I
e e
Environmental conditions (damp heat) °C/RH 12 + 12 cycle with 55 °C/90 - 96 % and 12 + 12 cycle with 55 °C/90 - 96 % and
acc. to IEC/EN 60068-2-30 25 °C/95 - 100 % 25 °C/95 - 100 %
Environmental conditions (dry heat) °C/RH 16 hours 55 °C/2 hours 70 °C with damp 16 hours 55 °C/2 hours 70 °C with
acc. to IEC/EN 60068-2-2 Test B heat 55 % damp heat 55 %
Ambient temperature °C -25 … +60 -25 … +60
Storage temperature °C -40 … +70 -40 … +70
Installation
Terminal Failsafe cage or ringlug terminal Failsafe cage or ringlug terminal
Connections (top/bottom) - C only mm 2 1 … 50 stranded 1 … 50 stranded
u
1 … 70 flexible 1 … 70 flexible
Tightening torque Nm 3.5 3.5
in-Ibs. 31 31
Screwdriver POZI 2 POZI 2
Mounting any any
Mounting position any any
Supply any any
(taking into account the polarization) (taking into account the polarization)
Dimensions and weight
Pole dimensions (H x L x W) mm 95 x 26.5 x 82.5 95 x 26.5 x 82.5
Pole weight g 240 240
* The pollution degree of the product, as defined in standard IEC 60947-1, is related to its micro environment, to which equipment is exposed. It may be different from that of
the macro-environment. According to where the equipment is located, the pollution degree of the macro environment can be considered up to category IV, if protection is
offered by means of such as an adequate enclosure or internal heating to prevent absorption or condensation of moisture.