2/8              ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
  2
          RCCBs
          F200 technical features




                                                                                                                                 F200 AC        F200 A         F200 A AP-R    F200 A S       F200 A 110V   F200 A 400 Hz  F200 A 16 2/3 Hz
                                              Standards                                                                          IEC/EN 61008-1; IEC/EN 61008-2-1, UL 1053                  IEC 61008-1; IEC   IEC/EN 61008-1;   IEC/EN 61008-1;
                                                                                                                                                                                             61008-2-1; UL 1053 IEC/EN 61008-2-1  IEC/EN 61008-2-1
                                    Electrical   Type (wave form of the earth leakage sensed)                                    AC             A              A              A              A             A             A
                                    features  Poles                                                                              2P , 4P (for 125 A only 4P)                                2P, 4P        4P            2P, 4P
                                              Rated current In                                              A                    16, 25, 40, 63, 80, 100, 125  25, 40, 63, 80, 100,   40, 63, 80, 100, 125  25, 40, 63, 80, 100  25, 40  63
                                                                                                                                                               125
                                              Rated sensitivity IDn                                         A                    0.01-0.03-0.1-0.3-0.5         0.03           0.1-0.3-0.5-1  0.03          0.03          0.03-0.3-0.5
                                              Rated voltage Ue                IEC                           V                    230/400 - 240/415
                                                                              UL/CSA                        V                    480Y/277 (up to 100 A)                                      -             -
                                              Insulation voltage Ui                                         V                    500
                                              Operating voltage of circuit test Ut  IEC                     V                    In ≤ 100; Right neutral: 110 (170 for 30mA) - 254 e; Left neutral: 195 (250 for 30 mA) -   110-254  170-254  110 (170 for
                                                                                                                                 440 e                                                                                   30 mA) - 254
                                                                                                                                 In = 125 A; Right neutral: 185 (150 for 30 mA) - 440 (250 for 30 mA) e;
                                                                                                                                 Left neutral: 195 (250 for 30 mA) - 440
                                                                              UL/CSA                        V                    In ≤ 100; Right neutral: 110 (170 for 30mA) - 277 e; Left neutral: 195 (250 for 30 mA) - 480 e d  -
                                              Rated frequency                                               Hz                   50…60                                                                     50...400      16 2/3
                                              Rated conditional short-circuit current    SCPD - fuse gG 100 A  kA                10 (for 125 A fuse is gG 125 A)
                                              Inc=I∆c
                                              Rated residual breaking capacity  I∆m=Im                      kA                   1 (1.25 for 125 A)
                                              Rated impulse withstand voltage (1.2/50) Uimp                 kV                   4
                                              Dielectric test voltage at ind. freq. for 1 min.              kV                   2.5
                                              Overvoltage category                                                               III, disconnector abilities
                                              Surge current resistance (wave 8/20)                          A                    NA                            3000           5000           NA            NA            NA
                                    Mechanical   Toggle                                                                          blue sealable in ON-OFF position
                                    features   Contact position indicator (CPI)                                                  yes
                                              Electrical life                                                                    10000 (2000 for 125 A)                                      10000         10000         10000
                                              Mechanical life                                                                    20000 (5000 for 125 A)                                      20000         20000         20000
                                              Protection degree               housing                                            IP4X
                                                                              terminals                                          IP2X
                                              Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30  °C/RH              28 cycles with 55°C/90-96% and 25°C/95-100%
                                              Ambient temperature (with daily average ≤   IEC               °C                   -25…+55 (-25...+40 for 125 A)                               -25...+55     -25...+55     -25...+55
                                              +35 °C)
                                              Storage temperature                                           °C                   -40…+70
                                    Installation  Terminal type                                                                  failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected) (cage for In > 63 A) b
                                              Terminal size top/bottom for cable  IEC                       mm 2                 25/25 (35/35 single slot terminal for In > 63 A)                          25/25         25/25
                                                                              UL/CSA                        AWG                  18-4 (up to 63 A)                                           -             -
                                              Terminal size top/bottom for busbar   IEC                     mm 2                 10/10 (not for In = 80-100 A)                                             10/10         10/10
                                                                              UL/CSA                        AWG                  18-8 (up to 63 A)                                           -             -
                                              Tightening torque               IEC                           Nm                   2.8 (3 for In = 125 A)                                      2.8           2.8           2.8
                                                                              UL/CSA                        in-lbs.              25 (up to 63 A)                                             -             -
                                              Tool                                                                               Nr. 2 Pozidriv
                                              Mounting                                                                           on DIN rail EN 60715 (35 mm) by means of fast clip device
                                              Mounting position                                                                  Any
                                              Connection                                                                         from top and bottom
                                              Withdrawal from busbar                                                             it is possible without using any tools only from the bottom (not for 125 A)
                                    Dimensions   Dimensions (H x D x W)       2P                            mm                   85 x 69 x 35                                                              -
                                    and weight                                4P                            mm                   85 x 69 x 70 (85 x 69.5 x 72 for 125 A)                                   85 x 69 x 70  85 x 69 x 70
                                              Weight                          2P                            g                    200                                                                       -
                                                                              4P                            g                    350 (380 for In = 80 and 100 A and 460 for In = 125A)                     350           350
                                    Combination  Combinable with:             auxiliary contact                                  yes (no for 125 A)                                                        yes           yes
                                    with                                      signal contact/auxiliary switch                    yes                                                                       yes           yes
                                    auxiliary                                 shunt trip                                         yes (no for 125 A)                                                        yes           yes
                                    elements
                                                                              undervoltage release                               yes (no for 125 A)                                                        yes           yes

                                     Ground-fault sensing and relaying equipment-component (up to 63 A)
                                    b prior to connection of aluminium conductors (≥ 4 mm 2 ) ensure that their contact points are cleaned, brushed and coated with grease
                                    c for S700-E/K 100A, S750-E 63A, S750DR-E/K 63A and other SCPD coordination values see Chapter 3 of Solutions for electrical
                                        distribution in buildings - technical details
                                    d F200 left neutral has not the UL certification and the UL mark
                                    e Only for versions with marking according to EN 61008-1; EN 61008-2-1
                                     Neutral conductor can be wired anywhere for 2P devices