Page 201 - Din prodcuts 2020
P. 201
2/9
— 2
RCCBs
F200 technical features
F200 AC F200 A F200 A AP-R F200 A S F200 A 110V F200 A 400 Hz F200 A 16 2/3 Hz
Standards IEC/EN 61008-1; IEC/EN 61008-2-1, UL 1053 IEC 61008-1; IEC IEC/EN 61008-1; IEC/EN 61008-1;
61008-2-1; UL 1053 IEC/EN 61008-2-1 IEC/EN 61008-2-1
Electrical Type (wave form of the earth leakage sensed) AC A A A A A A
features Poles 2P , 4P (for 125 A only 4P) 2P, 4P 4P 2P, 4P
Rated current In A 16, 25, 40, 63, 80, 100, 125 25, 40, 63, 80, 100, 40, 63, 80, 100, 125 25, 40, 63, 80, 100 25, 40 63
125
Rated sensitivity IDn A 0.01-0.03-0.1-0.3-0.5 0.03 0.1-0.3-0.5-1 0.03 0.03 0.03-0.3-0.5
Rated voltage Ue IEC V 230/400 - 240/415
UL/CSA V 480Y/277 (up to 100 A) - -
Insulation voltage Ui V 500
Operating voltage of circuit test Ut IEC V In ≤ 100; Right neutral: 110 (170 for 30mA) - 254 e; Left neutral: 195 (250 for 30 mA) - 110-254 170-254 110 (170 for
440 e 30 mA) - 254
In = 125 A; Right neutral: 185 (150 for 30 mA) - 440 (250 for 30 mA) e;
Left neutral: 195 (250 for 30 mA) - 440
UL/CSA V In ≤ 100; Right neutral: 110 (170 for 30mA) - 277 e; Left neutral: 195 (250 for 30 mA) - 480 e d -
Rated frequency Hz 50…60 50...400 16 2/3
Rated conditional short-circuit current SCPD - fuse gG 100 A kA 10 (for 125 A fuse is gG 125 A)
Inc=I∆c
Rated residual breaking capacity I∆m=Im kA 1 (1.25 for 125 A)
Rated impulse withstand voltage (1.2/50) Uimp kV 4
Dielectric test voltage at ind. freq. for 1 min. kV 2.5
Overvoltage category III, disconnector abilities
Surge current resistance (wave 8/20) A NA 3000 5000 NA NA NA
Mechanical Toggle blue sealable in ON-OFF position
features Contact position indicator (CPI) yes
Electrical life 10000 (2000 for 125 A) 10000 10000 10000
Mechanical life 20000 (5000 for 125 A) 20000 20000 20000
Protection degree housing IP4X
terminals IP2X
Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30 °C/RH 28 cycles with 55°C/90-96% and 25°C/95-100%
Ambient temperature (with daily average ≤ IEC °C -25…+55 (-25...+40 for 125 A) -25...+55 -25...+55 -25...+55
+35 °C)
Storage temperature °C -40…+70
Installation Terminal type failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected) (cage for In > 63 A) b
Terminal size top/bottom for cable IEC mm 2 25/25 (35/35 single slot terminal for In > 63 A) 25/25 25/25
UL/CSA AWG 18-4 (up to 63 A) - -
Terminal size top/bottom for busbar IEC mm 2 10/10 (not for In = 80-100 A) 10/10 10/10
UL/CSA AWG 18-8 (up to 63 A) - -
Tightening torque IEC Nm 2.8 (3 for In = 125 A) 2.8 2.8 2.8
UL/CSA in-lbs. 25 (up to 63 A) - -
Tool Nr. 2 Pozidriv
Mounting on DIN rail EN 60715 (35 mm) by means of fast clip device
Mounting position Any
Connection from top and bottom
Withdrawal from busbar it is possible without using any tools only from the bottom (not for 125 A)
Dimensions Dimensions (H x D x W) 2P mm 85 x 69 x 35 -
and weight 4P mm 85 x 69 x 70 (85 x 69.5 x 72 for 125 A) 85 x 69 x 70 85 x 69 x 70
Weight 2P g 200 -
4P g 350 (380 for In = 80 and 100 A and 460 for In = 125A) 350 350
Combination Combinable with: auxiliary contact yes (no for 125 A) yes yes
with signal contact/auxiliary switch yes yes yes
auxiliary shunt trip yes (no for 125 A) yes yes
elements
undervoltage release yes (no for 125 A) yes yes
Ground-fault sensing and relaying equipment-component (up to 63 A)
b prior to connection of aluminium conductors (≥ 4 mm 2 ) ensure that their contact points are cleaned, brushed and coated with grease
c for S700-E/K 100A, S750-E 63A, S750DR-E/K 63A and other SCPD coordination values see Chapter 3 of Solutions for electrical
distribution in buildings - technical details
d F200 left neutral has not the UL certification and the UL mark
e Only for versions with marking according to EN 61008-1; EN 61008-2-1
Neutral conductor can be wired anywhere for 2P devices