Page 201 - Din prodcuts 2020
P. 201

2/9




          —                                                                                                            2
          RCCBs
          F200 technical features




          F200 AC        F200 A         F200 A AP-R    F200 A S       F200 A 110V   F200 A 400 Hz  F200 A 16 2/3 Hz
 Standards  IEC/EN 61008-1; IEC/EN 61008-2-1, UL 1053                IEC 61008-1; IEC   IEC/EN 61008-1;   IEC/EN 61008-1;
                                                                      61008-2-1; UL 1053 IEC/EN 61008-2-1  IEC/EN 61008-2-1
 Electrical   Type (wave form of the earth leakage sensed)  AC  A  A  A  A          A             A
 features  Poles  2P , 4P (for 125 A only 4P)                        2P, 4P        4P            2P, 4P
 Rated current In  A  16, 25, 40, 63, 80, 100, 125  25, 40, 63, 80, 100,   40, 63, 80, 100, 125  25, 40, 63, 80, 100  25, 40  63
                                        125
 Rated sensitivity IDn  A  0.01-0.03-0.1-0.3-0.5  0.03  0.1-0.3-0.5-1  0.03         0.03          0.03-0.3-0.5
 Rated voltage Ue  IEC  V  230/400 - 240/415
 UL/CSA  V  480Y/277 (up to 100 A)                                    -             -
 Insulation voltage Ui  V  500
 Operating voltage of circuit test Ut  IEC  V  In ≤ 100; Right neutral: 110 (170 for 30mA) - 254 e; Left neutral: 195 (250 for 30 mA) -   110-254  170-254  110 (170 for
          440 e                                                                                   30 mA) - 254
          In = 125 A; Right neutral: 185 (150 for 30 mA) - 440 (250 for 30 mA) e;
          Left neutral: 195 (250 for 30 mA) - 440
 UL/CSA  V  In ≤ 100; Right neutral: 110 (170 for 30mA) - 277 e; Left neutral: 195 (250 for 30 mA) - 480 e d  -
 Rated frequency  Hz  50…60                                                         50...400      16 2/3
 Rated conditional short-circuit current    SCPD - fuse gG 100 A  kA  10 (for 125 A fuse is gG 125 A)
 Inc=I∆c
 Rated residual breaking capacity  I∆m=Im  kA  1 (1.25 for 125 A)
 Rated impulse withstand voltage (1.2/50) Uimp  kV  4
 Dielectric test voltage at ind. freq. for 1 min.  kV  2.5
 Overvoltage category  III, disconnector abilities
 Surge current resistance (wave 8/20)  A  NA  3000     5000           NA            NA            NA
 Mechanical   Toggle  blue sealable in ON-OFF position
 features   Contact position indicator (CPI)  yes
 Electrical life  10000 (2000 for 125 A)                              10000         10000         10000
 Mechanical life  20000 (5000 for 125 A)                              20000         20000         20000
 Protection degree  housing  IP4X
 terminals  IP2X
 Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30  °C/RH  28 cycles with 55°C/90-96% and 25°C/95-100%
 Ambient temperature (with daily average ≤   IEC  °C  -25…+55 (-25...+40 for 125 A)  -25...+55  -25...+55  -25...+55
 +35 °C)
 Storage temperature  °C  -40…+70
 Installation  Terminal type  failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected) (cage for In > 63 A) b
 Terminal size top/bottom for cable  IEC  mm 2  25/25 (35/35 single slot terminal for In > 63 A)  25/25  25/25
 UL/CSA  AWG  18-4 (up to 63 A)                                       -             -
 Terminal size top/bottom for busbar   IEC  mm 2  10/10 (not for In = 80-100 A)     10/10         10/10
 UL/CSA  AWG  18-8 (up to 63 A)                                       -             -
 Tightening torque  IEC  Nm  2.8 (3 for In = 125 A)                   2.8           2.8           2.8
 UL/CSA  in-lbs.  25 (up to 63 A)                                     -             -
 Tool     Nr. 2 Pozidriv
 Mounting  on DIN rail EN 60715 (35 mm) by means of fast clip device
 Mounting position  Any
 Connection  from top and bottom
 Withdrawal from busbar  it is possible without using any tools only from the bottom (not for 125 A)
 Dimensions   Dimensions (H x D x W)  2P   mm  85 x 69 x 35                         -
 and weight  4P   mm  85 x 69 x 70 (85 x 69.5 x 72 for 125 A)                       85 x 69 x 70  85 x 69 x 70
 Weight  2P   g  200                                                                -
 4P  g    350 (380 for In = 80 and 100 A and 460 for In = 125A)                     350           350
 Combination  Combinable with:   auxiliary contact  yes (no for 125 A)              yes           yes
 with   signal contact/auxiliary switch  yes                                        yes           yes
 auxiliary   shunt trip  yes (no for 125 A)                                         yes           yes
 elements
 undervoltage release  yes (no for 125 A)                                           yes           yes

  Ground-fault sensing and relaying equipment-component (up to 63 A)
 b prior to connection of aluminium conductors (≥ 4 mm 2 ) ensure that their contact points are cleaned, brushed and coated with grease
 c for S700-E/K 100A, S750-E 63A, S750DR-E/K 63A and other SCPD coordination values see Chapter 3 of Solutions for electrical
     distribution in buildings - technical details
 d F200 left neutral has not the UL certification and the UL mark
 e Only for versions with marking according to EN 61008-1; EN 61008-2-1
  Neutral conductor can be wired anywhere for 2P devices
   196   197   198   199   200   201   202   203   204   205   206