2/28             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
  2
          RCCBs
          F 200 series - F technical features




                                                                                                                                 F200 Type F                       DS201 M Type F                    DDA200 Type F
                                              Standards                                                                          IEC/EN 61008, IEC/EN 62423 2 ed   IEC/EN 61009, IEC/EN 62423 2 ed   IEC/EN 61009 App.G, IEC/EN 62423 2 ed
                                                                                                                                                                                       nd
                                                                                                                                                     nd
                                                                                                                                                                                                                              nd
                                    Electrical   Type                                                                            F
                                    features
                                              Number of poles                                                                    2P, 4P                            1P+N                              2P
                                                                                                                                                                                                          1
                                              Rated current I                                                                    25, 40, 63 A                      6 ≤ In ≤ 40 A                     40, 63 A  (to mount with MCB with In = 0,5…63A)
                                                        n
                                              Rated sensitivity I ∆n                                                             0.03 A
                                              Rated voltage U                                                                    2P: 230 V - 4P: 400 V             230 V                             230 V
                                                         e
                                              Insulation voltage U i                                                             500 V
                                              Max. / Min. operating voltage of circuit test                                      254 V / 170 V
                                              Rated frequency                                                                    50…60 Hz
                                              Rated breaking capacity acc. to IEC/EN 61009  ultimate Icn                         -                                 10000 A                           same as coupled MCB
                                              Rated breaking capacity              ultimate Icu                                  -                                 10 kA                             same as coupled MCB
                                              acc. to IEC/EN 60947-2 1P+N @230 VAC
                                                                                   service Ics                                   -                                 7.5 kA                            same as coupled MCB
                                              Rated residual breaking capacity I ∆m                                              1 kA                              6 kA                              same as coupled MCB
                                              Rated conditional short-circuit current Inc=I  SCPD - fuse gG 100 A                10kA                              -                                 -
                                                                           Δc
                                              Rated impulse withstand voltage (1.2/50) U imp                                     4 kV
                                              Dielectric test voltage at ind. freq. for 1 min.                                   2.5 kV
                                              Thermomagnetic release characteristic  B: 3 In ≤ Im ≤ 5 In                         -                                 n                                 same as coupled MCB
                                                                                   C: 5 In ≤ Im ≤ 10 In                          -                                 n                                 same as coupled MCB
                                              Surge current resistance (wave 8/20)                                               3000 A
                                    Mechanical   Toggle                                                                          blue sealable in ON-OFF position  black sealable in ON-OFF position  blue sealable in ON-OFF position
                                    features
                                              Flag indicators                      contact position indicator (green/red)        yes                               yes                               On MCB
                                                                                                                                                                                                     Indication with levers position:
                                                                                   differential trip indicator                   lever position                    yes                               - Both MCB/RCD block down: RCD tripping
                                                                                                                                                                                                     - MCB down, RCD block up: MCB tripping
                                              Electrical life                                                                    10 000 cycles
                                              Mechanical life                                                                    20 000 cycles
                                              Protection degree                    housing                                       IP4X
                                                                                   terminal                                      IP2X
                                              Environmental conditions (damp heat)                                               28 cycles with 55°C/90-96% and 25°C/95-100% [°C/RH]
                                              acc. to IEC/EN 60068-2-30
                                              Reference temperature for setting of thermal element                               -                                 30 °C                             -
                                              Ambient temperature (with daily average ≤ +35 °C)                                  -25…+55 °C
                                              Storage temperature                                                                -40…+70 °C
                                    Installation                                                                                                                                                     Top: failsafe bi-directional cylinder-lift terminal
                                                                                                                                                                                                     (shock protected)
                                              Terminal type                                                                      failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected)
                                                                                                                                                                                                     Bottom: failsafe cylinder-lift terminal
                                                                                                                                                                                                     (shock protected)
                                              Terminal size top/bottom for cables                                                25/25 mm 2
                                              Terminal size top/bottom for busbar                                                10/10 mm 2                                                          10/- mm 2
                                              Tightening torque top/bottom                                                       2.8 Nm
                                              Tool                                                                               N°2 Pozidriv
                                              Mounting                                                                           on DIN rail EN 60715 (35 mm) by means of fast clip device
                                              Connection                                                                         from top and bottom
                                    Dimensions    Dimensions (H x D x W)                                                         2P: 85 x 69 x 35 mm; 4P: 85 x 69 x 70 mm  1P+N: 85 x 67 x 35 mm     2P: 93 x 69 x 69,5 mm
                                    and weight  Weight                                                                           2P: 225 g; 4P: 375 g              1P+N: 240 g                       2P: 180 g
                                    Combination
                                    with auxiliary  Combinable with:                                                             auxiliary contact, signal contact, shunt trip, undervoltage release (see next pages)
                                    elements

                                    1  RCD-blocks DDA 200 with rated current 63 A are provided with two additional terminals for remote tripping.