Page 220 - Din prodcuts 2020
P. 220
2/28 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
2
RCCBs
F 200 series - F technical features
F200 Type F DS201 M Type F DDA200 Type F
Standards IEC/EN 61008, IEC/EN 62423 2 ed IEC/EN 61009, IEC/EN 62423 2 ed IEC/EN 61009 App.G, IEC/EN 62423 2 ed
nd
nd
nd
Electrical Type F
features
Number of poles 2P, 4P 1P+N 2P
1
Rated current I 25, 40, 63 A 6 ≤ In ≤ 40 A 40, 63 A (to mount with MCB with In = 0,5…63A)
n
Rated sensitivity I ∆n 0.03 A
Rated voltage U 2P: 230 V - 4P: 400 V 230 V 230 V
e
Insulation voltage U i 500 V
Max. / Min. operating voltage of circuit test 254 V / 170 V
Rated frequency 50…60 Hz
Rated breaking capacity acc. to IEC/EN 61009 ultimate Icn - 10000 A same as coupled MCB
Rated breaking capacity ultimate Icu - 10 kA same as coupled MCB
acc. to IEC/EN 60947-2 1P+N @230 VAC
service Ics - 7.5 kA same as coupled MCB
Rated residual breaking capacity I ∆m 1 kA 6 kA same as coupled MCB
Rated conditional short-circuit current Inc=I SCPD - fuse gG 100 A 10kA - -
Δc
Rated impulse withstand voltage (1.2/50) U imp 4 kV
Dielectric test voltage at ind. freq. for 1 min. 2.5 kV
Thermomagnetic release characteristic B: 3 In ≤ Im ≤ 5 In - n same as coupled MCB
C: 5 In ≤ Im ≤ 10 In - n same as coupled MCB
Surge current resistance (wave 8/20) 3000 A
Mechanical Toggle blue sealable in ON-OFF position black sealable in ON-OFF position blue sealable in ON-OFF position
features
Flag indicators contact position indicator (green/red) yes yes On MCB
Indication with levers position:
differential trip indicator lever position yes - Both MCB/RCD block down: RCD tripping
- MCB down, RCD block up: MCB tripping
Electrical life 10 000 cycles
Mechanical life 20 000 cycles
Protection degree housing IP4X
terminal IP2X
Environmental conditions (damp heat) 28 cycles with 55°C/90-96% and 25°C/95-100% [°C/RH]
acc. to IEC/EN 60068-2-30
Reference temperature for setting of thermal element - 30 °C -
Ambient temperature (with daily average ≤ +35 °C) -25…+55 °C
Storage temperature -40…+70 °C
Installation Top: failsafe bi-directional cylinder-lift terminal
(shock protected)
Terminal type failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected)
Bottom: failsafe cylinder-lift terminal
(shock protected)
Terminal size top/bottom for cables 25/25 mm 2
Terminal size top/bottom for busbar 10/10 mm 2 10/- mm 2
Tightening torque top/bottom 2.8 Nm
Tool N°2 Pozidriv
Mounting on DIN rail EN 60715 (35 mm) by means of fast clip device
Connection from top and bottom
Dimensions Dimensions (H x D x W) 2P: 85 x 69 x 35 mm; 4P: 85 x 69 x 70 mm 1P+N: 85 x 67 x 35 mm 2P: 93 x 69 x 69,5 mm
and weight Weight 2P: 225 g; 4P: 375 g 1P+N: 240 g 2P: 180 g
Combination
with auxiliary Combinable with: auxiliary contact, signal contact, shunt trip, undervoltage release (see next pages)
elements
1 RCD-blocks DDA 200 with rated current 63 A are provided with two additional terminals for remote tripping.