Page 221 - Din prodcuts 2020
P. 221

2/29




          —                                                                                                            2
          RCCBs
          F 200 series - F technical features




          F200 Type F                       DS201 M Type F                    DDA200 Type F
 Standards  IEC/EN 61008, IEC/EN 62423 2 ed  IEC/EN 61009, IEC/EN 62423 2 ed  IEC/EN 61009 App.G, IEC/EN 62423 2 ed
                              nd
                                                                nd
                                                                                                      nd
 Electrical   Type  F
 features
 Number of poles  2P, 4P                    1P+N                              2P
 Rated current I  25, 40, 63 A              6 ≤ In ≤ 40 A                     40, 63 A  (to mount with MCB with In = 0,5…63A)
                                                                                   1
 n
 Rated sensitivity I ∆n  0.03 A
 Rated voltage U  2P: 230 V - 4P: 400 V     230 V                             230 V
 e
 Insulation voltage U i  500 V
 Max. / Min. operating voltage of circuit test  254 V / 170 V
 Rated frequency  50…60 Hz
 Rated breaking capacity acc. to IEC/EN 61009  ultimate Icn  -  10000 A       same as coupled MCB
 Rated breaking capacity    ultimate Icu  -  10 kA                            same as coupled MCB
 acc. to IEC/EN 60947-2 1P+N @230 VAC
 service Ics  -                             7.5 kA                            same as coupled MCB
 Rated residual breaking capacity I ∆m  1 kA  6 kA                            same as coupled MCB
 Rated conditional short-circuit current Inc=I  SCPD - fuse gG 100 A  10kA  -  -
 Δc
 Rated impulse withstand voltage (1.2/50) U imp  4 kV
 Dielectric test voltage at ind. freq. for 1 min.  2.5 kV
 Thermomagnetic release characteristic  B: 3 In ≤ Im ≤ 5 In  -  n             same as coupled MCB
 C: 5 In ≤ Im ≤ 10 In  -                    n                                 same as coupled MCB
 Surge current resistance (wave 8/20)  3000 A
 Mechanical   Toggle  blue sealable in ON-OFF position  black sealable in ON-OFF position  blue sealable in ON-OFF position
 features
 Flag indicators  contact position indicator (green/red)  yes  yes            On MCB
                                                                              Indication with levers position:
 differential trip indicator  lever position  yes                             - Both MCB/RCD block down: RCD tripping
                                                                              - MCB down, RCD block up: MCB tripping
 Electrical life  10 000 cycles
 Mechanical life  20 000 cycles
 Protection degree  housing  IP4X
 terminal  IP2X
 Environmental conditions (damp heat)    28 cycles with 55°C/90-96% and 25°C/95-100% [°C/RH]
 acc. to IEC/EN 60068-2-30
 Reference temperature for setting of thermal element  -  30 °C               -
 Ambient temperature (with daily average ≤ +35 °C)  -25…+55 °C
 Storage temperature  -40…+70 °C
 Installation                                                                 Top: failsafe bi-directional cylinder-lift terminal
                                                                              (shock protected)
 Terminal type  failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected)
                                                                              Bottom: failsafe cylinder-lift terminal
                                                                              (shock protected)
 Terminal size top/bottom for cables  25/25 mm 2
 Terminal size top/bottom for busbar  10/10 mm 2                              10/- mm 2
 Tightening torque top/bottom  2.8 Nm
 Tool     N°2 Pozidriv
 Mounting  on DIN rail EN 60715 (35 mm) by means of fast clip device
 Connection  from top and bottom
 Dimensions    Dimensions (H x D x W)  2P: 85 x 69 x 35 mm; 4P: 85 x 69 x 70 mm  1P+N: 85 x 67 x 35 mm  2P: 93 x 69 x 69,5 mm
 and weight  Weight  2P: 225 g; 4P: 375 g   1P+N: 240 g                       2P: 180 g
 Combination
 with auxiliary  Combinable with:  auxiliary contact, signal contact, shunt trip, undervoltage release (see next pages)
 elements

 1  RCD-blocks DDA 200 with rated current 63 A are provided with two additional terminals for remote tripping.
   216   217   218   219   220   221   222   223   224   225   226