DDA 200 technical features
DDA 200 AC DDA 200 A DDA 200 A AP-R DDA 200 A AE DDA 200 A S DDA 200 B
Standards IEC/EN 61009-1 Ann. G; IEC/EN 61009-2-1 IEC/EN 61009-1 Ann. G;
IEC/EN 61009-2-1,
IEC EN 62423
Operating characteristic: type AC A A A A B
Rated current In [A] 25, 40, 63 25, 40, 63 63 b 63 25-40-63
Poles 2P, 3P, 4P 2P, 3P, 4P
Rated voltage Ue 2P [V] 230 (400 for special execution @400 V) 230 230 230
DDA 200 3P 230/400 400 400 400
4P 230/400 230/400 230/400 230/400
Insulation voltage Ui [V] 500
Operating voltage of circuit test Ut 2P [V] 110-254 for special execution @110V; 184-264 195-254 (170-254 for 30 195-254 (170-254 for 30
195-254 (170-254 for 30 mA; 400 for special execution @400 V) mA) mA)
3P 195-440 (300-440 for 30 mA; 110-254 for special execution @110 V) 310-440 195-440 (300-440 for 310-440 (300-440 for 30
30 mA) mA)
4P 195-440 (300-440 for 30 mA; 110-254 for special execution @110 V) 184-264 195-440 (300-440 for 195-254 (300-440 for 30
30 mA) mA)
Rated frequency Hz 50…60
Rated breaking capacity according to IEC EN 61009 [A] same of the coupled MCB
Rated breaking capacity according to IEC EN 60947-2 [A] same of the coupled MCB
Rated residual breaking capacity I∆m [kA] same of the coupled MCB
Rated inpulse withstand capacity (1,2/50) Uimp [kV] 4
Dielectric test voltage at ind. freq. for 1 min. [kV] 2,5
Surge current resistance (wave 8/20) [A] 3000 (5000 for selective
NA 3000 NA 5000
types)
Rated sensitivity I∆n [A] 0.01-0.03-0.1-0.3-0.5-1 0.03 0.03-0.3-0.5-1 0.1-0.3-0.5-1 0.03 - 0.3 - 0.5
Toggle blue
Electrical life 10000
Mechanical life 20000
Protection degree housing IP4X
terminals IP2X
Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30 [°C/RH] 28 cycles with 55°C/90-96% and 25°C/95-100%
Ambient temperature (with daily average ≤ +35 °C) [°C] -25...+55
Storage temperature [°C] -40…+70
Terminal type 2P bi-directional cylinder-lift
3P/4P In=25 and 40 A cage type -
3P/4P In=63 A bi-directional cylinder-lift
2
Terminal size 2P [mm ] (rigid or flexible) up to 25
3P/4P In=25 and 40 A [mm ] (rigid or flexible) up to 16 -
2
3P/4P In=63 A [mm ] (rigid or flexible) up to 25
2
Tightening torque 2P [Nm] 2.8
3P/4P In=25 and 40 A [Nm] 1.2 -
3P/4P In=63 A [Nm] 2.8
Mounting on DIN rail EN 60715 (35 mm) by means of fast clip device
Mounting position Any
Dimensions 2P [mm] 85 x 69 x 35 85 x 69 x 70
H x P x L 3P/4P In=25 and 40 A [mm] 85 x 69 x 35 85 x 69 x 70
3P/4P In=63 A [mm] 85 x 69 x 70 85 x 69 x 70
Weight 2P [g] 175 350
3P/4P In=25 and 40 A [g] 175 375
3P/4P In=63 A [g] 325 395
Combinable with S 200 L yes
S 200 yes
S 200 M yes
S 200 P yes
All RCD-blocks DDA 200 with rated current 63 A are provided with two additional terminals for remote tripping.
b DDA200 A AE is provided with two additional terminals for remote release in positive safety.
A remote control circuit should be connected to those terminals where circuit breakers or push buttons
with normally closed contacts should be inserted.