Page 235 - Din prodcuts 2020
P. 235

2/43




          —                                                                                                            2
          RCD-blocks
          DDA 200 technical features




          DDA 200 AC       DDA 200 A        DDA 200 A AP-R  DDA 200 A AE    DDA 200 A S       DDA 200 B
 Standards  IEC/EN 61009-1 Ann. G; IEC/EN 61009-2-1                                           IEC/EN 61009-1 Ann. G;
                                                                                              IEC/EN 61009-2-1,
                                                                                              IEC EN 62423
 Operating characteristic: type  AC  A      A              A                A                 B
 Rated current In  [A]  25, 40, 63         25, 40, 63    63 b             63               25-40-63
 Poles    2P, 3P, 4P                                                                          2P, 3P, 4P
 Rated voltage Ue  2P  [V]  230 (400 for special execution @400 V)   230    230               230
 3P       230/400                                          400              400               400
 4P       230/400                                          230/400          230/400           230/400
 Insulation voltage Ui  [V]  500
 Operating voltage of circuit test Ut  2P  [V]  110-254 for special execution @110V;    184-264  195-254 (170-254 for 30  195-254 (170-254 for 30
          195-254 (170-254 for 30 mA; 400 for special execution @400 V)     mA)               mA)
 3P       195-440 (300-440 for 30 mA; 110-254 for special execution @110 V)  310-440  195-440 (300-440 for   310-440 (300-440 for 30
                                                                            30 mA)            mA)
 4P       195-440 (300-440 for 30 mA; 110-254 for special execution @110 V)  184-264  195-440 (300-440 for   195-254 (300-440 for 30
                                                                            30 mA)            mA)
 Rated frequency  Hz  50…60
 Rated breaking capacity according to  IEC EN 61009  [A]  same of the coupled MCB
 Rated breaking capacity according to  IEC EN 60947-2  [A]  same of the coupled MCB
 Rated residual breaking capacity  I∆m  [kA]  same of the coupled MCB
 Rated inpulse withstand capacity (1,2/50) Uimp  [kV]  4
 Dielectric test voltage at ind. freq. for 1 min.  [kV]  2,5
 Surge current resistance (wave 8/20)  [A]                                                    3000 (5000 for selective
          NA                                3000           NA               5000
                                                                                              types)
 Rated sensitivity I∆n  [A]  0.01-0.03-0.1-0.3-0.5-1  0.03  0.03-0.3-0.5-1  0.1-0.3-0.5-1     0.03 - 0.3 - 0.5
 Toggle   blue
 Electrical life  10000
 Mechanical life  20000
 Protection degree  housing  IP4X
 terminals  IP2X
 Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30  [°C/RH]  28 cycles with 55°C/90-96% and 25°C/95-100%
 Ambient temperature (with daily average ≤ +35 °C)  [°C]  -25...+55
 Storage temperature  [°C]  -40…+70
 Terminal type  2P   bi-directional cylinder-lift
 3P/4P In=25 and 40 A  cage type                                                              -
 3P/4P In=63 A  bi-directional cylinder-lift
 Terminal size  2P   [mm ] 2  (rigid or flexible) up to 25
 3P/4P In=25 and 40 A  [mm ] 2  (rigid or flexible) up to 16                                  -
 3P/4P In=63 A  [mm ] 2  (rigid or flexible) up to 25
 Tightening torque  2P   [Nm]  2.8
 3P/4P In=25 and 40 A  [Nm]  1.2                                                              -
 3P/4P In=63 A  [Nm]  2.8
 Mounting  on DIN rail EN 60715 (35 mm) by means of fast clip device
 Mounting position  Any
 Dimensions   2P   [mm]  85 x 69 x 35                                                         85 x 69 x 70
 H x P x L  3P/4P In=25 and 40 A  [mm]  85 x 69 x 35                                          85 x 69 x 70
 3P/4P In=63 A  [mm]  85 x 69 x 70                                                            85 x 69 x 70
 Weight  2P   [g]  175                                                                        350
 3P/4P In=25 and 40 A  [g]  175                                                               375
 3P/4P In=63 A  [g]  325                                                                      395
 Combinable with  S 200 L  yes
 S 200    yes
 S 200 M  yes
 S 200 P  yes
  All RCD-blocks DDA 200 with rated current 63 A are provided with two additional terminals for remote tripping.
 b DDA200 A AE is provided with two additional terminals for remote release in positive safety.
 A remote control circuit should be connected to those terminals where circuit breakers or push buttons
 with normally closed contacts should be inserted.
   230   231   232   233   234   235   236   237   238   239   240