          DS201 technical features
















                                                              DS201 L                  DS201                                     DS201 M                           DS201 M 110V                      DS201 T
                   Standards                                  IEC/EN 61009-1; IEC/EN 61009-2-1 IEC/EN 61009-1; IEC/EN 61009-2-1  IEC/EN 61009-1; IEC/EN 61009-2-1  IEC 61009-1; IEC 61009-2-1        IEC/EN 61009-1; IEC/EN 61009-2-1
          Electrical    Type (wave form of the earth leakage sensed)  A - AC - APR     A - AC - APR                              A - AC - APR - F                  A                                 A - APR
          features  Number of poles                           1P + N                   1P + N                                    1P + N                            1P + N                            1P + N
                   Rated current In                   A       6 ≤ In ≤ 32              1 ≤ In ≤ 40                               4 ≤ In ≤ 40                       6 ≤ In ≤ 40                       6 ≤ In ≤ 40
                   Rated sensitivity I∆n              A       0.01 - 0.03 - 0.3        0.01 - 0.03 - 0.1 - 0.3                   0.01 - 0.03 - 0.1 - 0.3           0.03                              0.03
                   Rated voltage Ue                   V       230-240                  230-240                                   230-240                           230-240                           230-240
                   Insulation voltage Ui              V       500 V AC                 500 V AC                                  500 V AC                          500 V AC                          500 V AC
                   Overvoltage category                       III                      III                                       III                               III                               III
                   Pollution degree                           2                        2                                         2                                 2                                 2
                   Operating voltage of circuit test   V      110 (170 for 30mA) - 264  110 (170 for 30mA) - 264                 110 (170 for 30mA) - 264          110 - 264                         170 - 264
                   Ut
                   Rated frequency                    Hz      50/60                    50/60                                     50/60                             50/60                             50/60
                   Rated breaking capacity    Icn     A       4500                     6000                                      10000                             10000                             6000
                   acc. to IEC/EN 61009-1
                   Rated breaking capacity    ultimate Icu  kA  6                      10                                        15                                15                                10
                   acc. to IEC/EN 60947-2 (only   service Ics  kA  4.5                 7.5                                       11.2                              11.2                              7.5
                   referring to short circuit test)
                   Rated residual breaking capacity  I∆m  A   4500                     6000                                      6000                              6000                              6000
                   I∆m according to EN 61009-1
                   Rated residual breaking capacity  I∆m  A   4500                     6000 up to 25 A; 4500 for 32A and         6000 up to 25 A; 4500 for 32A and 40A  6000 up to 25 A; 4500 for 32A and 40A  6000 up to 25 A; 4500 for 32A and 40A
                   I∆m according to IEC 61009-1                                        40A
                   Rated impulse withstand voltage (1.2/50) Uimp  kV  4 kV             4 kV                                      4 kV                              4 kV                              4 kV
                   Dielectric test voltage at ind. freq. for 1 min.  kV  2.5 kV (50 / 60Hz, 1 min.)  2.5 kV (50 / 60Hz, 1 min.)  2.5 kV (50 / 60Hz, 1 min.)        2.5 kV (50 / 60Hz, 1 min.)        2.5 kV (50 / 60Hz, 1 min.)
                   Thermomagnetic release -   B: 3 In ≤ In ≤ 5 In                      ■                                         ■                                 ■
                   characteristic         C: 5 In ≤ In ≤ 10   ■                        ■                                         ■                                 ■                                 ■
                                          In
                                          K: 10 In ≤ In ≤ 14                           ■                                         ■
                                          In
                   Energy limiting class acc. to              3                        3                                         3                                 NA                                3
                   EN 61009-1
                   Surge current resistance (wave     A       NA for A, AC versions; 3000 for APR  NA for A, AC versions; 3000 for APR   NA for A, AC versions; 3000 for APR and F version  NA       NA for A; 3000 for APR version
                   8/20)                                      version                  version
          Mechanical   Housing                                Insulation group I - II, RAL 7035  Insulation group I - II, RAL 7035  Insulation group I - II, RAL 7035  Insulation group I - II, RAL 7035  Insulation group I - II, RAL 7035
          features  Toggle                                    Insulation group II, Black RAL 9005,   Insulation group II, Black RAL 9005,    Insulation group II, Black RAL 9005,    Insulation group II, Black RAL 9005,    Insulation group II, Black RAL 9005,
                                                              sealable in ON-OFF positions  sealable in ON-OFF positions         sealable in ON-OFF positions      sealable in ON-OFF positions      sealable in ON-OFF positions
                   Contact position indication                Green/Red Window         Green/Red Window                          Green/Red Window                  Green/Red Window                  Green/Red Window
                   Earth fault trip indication                Blue flag on toggle      Blue flag on toggle                       Blue flag on toggle               Blue flag on toggle               Blue flag on toggle
                   Electrical life                    operations 10000                 10000                                     10000                             10000                             10000
                   Mechanical life                    operations 20000                 20000                                     20000                             20000                             20000
                   Protection degree acc. to EN   housing     IP4X                     IP4X                                      IP4X                              IP4X                              IP4X
                   60529                  terminals           IP2X                     IP2X                                      IP2X                              IP2X                              IP2X
                   Shock resistance acc. to IEC/EN            25g - 2 shocks - 13ms    25g - 2 shocks - 13ms                     25g - 2 shocks - 13ms             25g - 2 shocks - 13ms             25g - 2 shocks - 13ms
                   60068-2-27
                   Vibration resistance acc. to IEC/EN 60068-2-6  0.1 mm or 1 g - 20 cycles at   0.1 mm or 1 g - 20 cycles at    0.1 mm or 1 g - 20 cycles at 5…150…5 Hz  0.1 mm or 1 g - 20 cycles at 5…150…5 Hz  0.1 mm or 1 g - 20 cycles at 5…150…5 Hz
                                                              5…150…5 Hz               5…150…5 Hz
                   Environmental conditions (damp heat)    °C/RH  28 cycles with 55°C/90-96% and   28 cycles with 55°C/90-96% and   28 cycles with 55°C/90-96% and 25°C/95-100%  28 cycles with 55°C/90-96% and 25°C/95-100% 28 cycles with 55°C/90-96% and 25°C/95-100%
                   acc. to IEC/EN 60068-2-30                  25°C/95-100%             25°C/95-100%
                   Reference temperature for setting of thermal   °C  30               30 (20 for K tripping char)               30 (20 for K tripping char)       30                                30
                   element
                   Ambient temperature (with daily average ≤ +35 °C) °C  -25…+55       -25…+55                                   -25…+55                           -25…+55                           -25…+55
                   Storage temperature                °C       -40…+70                  -40…+70                                   -40…+70                           -40…+70                           -40…+70