Page 255 - Din prodcuts 2020
P. 255

2/63




          —                                                                                                            2
          RCBOs
          DS201 technical features
















 DS201 L  DS201  DS201 M                    DS201 M 110V                      DS201 T
 Standards  IEC/EN 61009-1; IEC/EN 61009-2-1 IEC/EN 61009-1; IEC/EN 61009-2-1  IEC/EN 61009-1; IEC/EN 61009-2-1  IEC 61009-1; IEC 61009-2-1  IEC/EN 61009-1; IEC/EN 61009-2-1
 Electrical    Type (wave form of the earth leakage sensed)  A - AC - APR  A - AC - APR  A - AC - APR - F  A  A - APR
 features  Number of poles  1P + N  1P + N  1P + N  1P + N                    1P + N
 Rated current In  A  6 ≤ In ≤ 32  1 ≤ In ≤ 40  4 ≤ In ≤ 40  6 ≤ In ≤ 40      6 ≤ In ≤ 40
 Rated sensitivity I∆n  A  0.01 - 0.03 - 0.3  0.01 - 0.03 - 0.1 - 0.3  0.01 - 0.03 - 0.1 - 0.3  0.03  0.03
 Rated voltage Ue  V  230-240  230-240  230-240  230-240                      230-240
 Insulation voltage Ui   V  500 V AC  500 V AC  500 V AC  500 V AC            500 V AC
 Overvoltage category  III  III  III        III                               III
 Pollution degree  2  2  2                  2                                 2
 Operating voltage of circuit test   V  110 (170 for 30mA) - 264  110 (170 for 30mA) - 264  110 (170 for 30mA) - 264  110 - 264  170 - 264
 Ut
 Rated frequency  Hz  50/60  50/60  50/60   50/60                             50/60
 Rated breaking capacity    Icn   A  4500  6000  10000  10000                 6000
 acc. to IEC/EN 61009-1
 Rated breaking capacity    ultimate Icu  kA  6  10  15  15                   10
 acc. to IEC/EN 60947-2 (only   service Ics  kA  4.5  7.5  11.2  11.2         7.5
 referring to short circuit test)
 Rated residual breaking capacity  I∆m  A  4500  6000  6000  6000             6000
 I∆m according to EN 61009-1
 Rated residual breaking capacity  I∆m  A  4500  6000 up to 25 A; 4500 for 32A and   6000 up to 25 A; 4500 for 32A and 40A  6000 up to 25 A; 4500 for 32A and 40A  6000 up to 25 A; 4500 for 32A and 40A
 I∆m according to IEC 61009-1  40A
 Rated impulse withstand voltage (1.2/50) Uimp  kV  4 kV  4 kV  4 kV  4 kV    4 kV
 Dielectric test voltage at ind. freq. for 1 min.  kV  2.5 kV (50 / 60Hz, 1 min.)  2.5 kV (50 / 60Hz, 1 min.)  2.5 kV (50 / 60Hz, 1 min.)  2.5 kV (50 / 60Hz, 1 min.)  2.5 kV (50 / 60Hz, 1 min.)
 Thermomagnetic release -   B: 3 In ≤ In ≤ 5 In  ■  ■  ■
 characteristic  C: 5 In ≤ In ≤ 10   ■  ■  ■  ■                               ■
 In
 K: 10 In ≤ In ≤ 14   ■  ■
 In
 Energy limiting class acc. to    3  3  3   NA                                3
 EN 61009-1
 Surge current resistance (wave   A  NA for A, AC versions; 3000 for APR  NA for A, AC versions; 3000 for APR   NA for A, AC versions; 3000 for APR and F version  NA  NA for A; 3000 for APR version
 8/20)  version  version
 Mechanical   Housing  Insulation group I - II, RAL 7035  Insulation group I - II, RAL 7035  Insulation group I - II, RAL 7035  Insulation group I - II, RAL 7035  Insulation group I - II, RAL 7035
 features  Toggle  Insulation group II, Black RAL 9005,   Insulation group II, Black RAL 9005,    Insulation group II, Black RAL 9005,    Insulation group II, Black RAL 9005,    Insulation group II, Black RAL 9005,
 sealable in ON-OFF positions  sealable in ON-OFF positions  sealable in ON-OFF positions  sealable in ON-OFF positions  sealable in ON-OFF positions
 Contact position indication  Green/Red Window   Green/Red Window   Green/Red Window   Green/Red Window   Green/Red Window
 Earth fault trip indication  Blue flag on toggle  Blue flag on toggle  Blue flag on toggle  Blue flag on toggle  Blue flag on toggle
 Electrical life  operations 10000  10000  10000  10000                       10000
 Mechanical life  operations 20000  20000  20000  20000                       20000
 Protection degree acc. to EN   housing  IP4X  IP4X  IP4X  IP4X               IP4X
 60529  terminals  IP2X  IP2X  IP2X         IP2X                              IP2X
 Shock resistance acc. to IEC/EN   25g - 2 shocks - 13ms  25g - 2 shocks - 13ms  25g - 2 shocks - 13ms  25g - 2 shocks - 13ms  25g - 2 shocks - 13ms
 60068-2-27
 Vibration resistance acc. to IEC/EN 60068-2-6  0.1 mm or 1 g - 20 cycles at   0.1 mm or 1 g - 20 cycles at   0.1 mm or 1 g - 20 cycles at 5…150…5 Hz  0.1 mm or 1 g - 20 cycles at 5…150…5 Hz  0.1 mm or 1 g - 20 cycles at 5…150…5 Hz
 5…150…5 Hz  5…150…5 Hz
 Environmental conditions (damp heat)    °C/RH  28 cycles with 55°C/90-96% and   28 cycles with 55°C/90-96% and   28 cycles with 55°C/90-96% and 25°C/95-100%  28 cycles with 55°C/90-96% and 25°C/95-100% 28 cycles with 55°C/90-96% and 25°C/95-100%
 acc. to IEC/EN 60068-2-30  25°C/95-100%  25°C/95-100%
 Reference temperature for setting of thermal   °C  30  30 (20 for K tripping char)  30 (20 for K tripping char)  30  30
 element
 Ambient temperature (with daily average ≤ +35 °C) °C  -25…+55  -25…+55  -25…+55  -25…+55  -25…+55
 Storage temperature  °C   -40…+70   -40…+70   -40…+70   -40…+70               -40…+70
   250   251   252   253   254   255   256   257   258   259   260