Page 303 - Din prodcuts 2020
P. 303

2/111




          —                                                                                                            2
          RCBOs
          DS 200 technical features




          DS 200 AC                 DS 200 A                   DS 200 M AC               DS 200 M A
 Standards  IEC/EN 61009-1; IEC/EN 61009-2-1; IEC/EN 60947-2
 Electrical  Operating characteristic: type (wave form of the earth leakage sensed)  AC  A  AC  A
 features  Poles  2P, 3P, 4P
 Rated sensitivity IDn  A  0.03
 Rated current In  A  6 ≤In ≤ 63 
 Rated voltage Ue  2P   V  230-240
 3P, 4P  V  230/400 - 240/415
 Insulation voltage Ui  V  500
 Operating voltage of circuit test Ut  2P   V  110 (170 for 30 mA) - 254
 3P   V   195 (300 for 30 mA) - 440
 4P   V   195 (300 for 30 mA) - 440
 Rated frequency  Hz  50…60
 Rated breaking capacity acc. to IEC/EN 61009  ultimate Icn  A  6000  6000  10000        10000
 Rated breaking capacity  ultimate Icu  kA  10  10             15                        15
 acc. to IEC/EN 60947-2  1P+N @230 VAC, 2P, 3P, 4P @400   service Ics  kA  7.5  7.5  11.2  11.2
 VAC
 Rated residual breaking capacity  I∆m  kA  6  6               10                        10
 Rated impulse withstand voltage (1.2/50) Uimp  kV  6
 Dielectric test voltage at ind. freq. for 1 min.  kV  2.5
 Overvoltage category  III, disconnector abilities
 Thermomagnetic release  B: 3 In ≤ Im ≤ 5 In  n  n             n                         n
 characteristic
 C: 5 In ≤ Im ≤ 10 In  n            n                          n                         n
 K: 10 In ≤ Im ≤ 14 In              n
 Surge current resistance (wave 8/20)  A  NA
 Mechanical   Toggle  2P, 3P, 4P  black (MCB) sealable in ON-OFF position + blue (RCD)
 features  Contact position indication  CPI on window
 Electrical life  10000
 Mechanical life  20000
 Protection degree  housing  IP4X
 terminals  IP2X
 Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30  °C/RH  28 cycles with 55°C/90-96% and 25°C/95-100%
 Reference temperature for setting of thermal element  °C  30
 Ambient temperature (with daily average ≤ +35 °C)  °C  -25…+55
 Storage temperature  °C  -40…+70
 Installation  Terminal type  top  failsafe bidirectional cylinder-lift terminal (shock protected) b
 bottom    2P  failsafe bidirectional cylinder-lift terminal (shock protected) b
                3P/4P In ≤ 40 A  cage (shock protected)
                3P/4P 50 A ≤ In ≤ 63 A  failsafe bidirectional cylinder-lift terminal (shock protected) b
 Terminal size top/bottom per cable  2P   mm 2  rigid: 35/25 flexible: 25/25
 3P/4P In ≤ 40 A  mm 2  rigid: 35/25 flexible: 25/16
 3P/4P 50 A ≤ In ≤ 63 A  mm 2  rigid : 35/25   flexible : 25/25
 Tightening torque top/bottom  2P   Nm  2.8/2.8
 3P/4P In ≤ 40 A  Nm  2.8/1.2
 3P/4P 50 A ≤ In ≤ 63 A  Nm  2.8/2.8
 Mounting  on DIN rail EN 60715 (35 mm) by means of fast clip device
 Mounting position  Any
 Connection  715 (35 mm) by means of fast clip devicefrom top and bottom
   298   299   300   301   302   303   304   305   306   307   308