Page 317 - Din prodcuts 2020
P. 317

2/125




          —                                                                                                            2
          RCBOs
          DS800 technical features




          DS800S A          DS800N A         DS800S A S       DS800N A S       DS800S A AP-R   DS800N A AP-R
 Standards    IEC/EN 60947-2
 Electrical    Operating characteristic: type (wave form of the earth leakage sensed)       A  A  A
 features    Poles       2P, 3P, 4P          2P,4P                             2P, 3P, 4P

    Rated sensitivity IDn    A    0.3        0.3-1(*)                          0.03
    Rated current In    A    125

 Rated voltage Ue   V    230/400-240/415-400/690
 Insulation voltage Ui    V    690
 Operating voltage of circuit test Ut    V  195-690
 Rated frequency   Hz    50…60
 Rated ultimate short-circuit breaking capacity Icu  240/415 V AC  kA    50  36  50  36  50    36
 254/440 V AC  kA    30     20               30               20               30              20
 289/500 V AC  kA    10     10               10               10               10              10
 400/690 V AC  kA    4.5    4.5              4.5              4.5              4.5             4.5
 Rated service short-circuit breaking capacity Ics  240/415 V AC  kA    40  30  40  30  40     30
 254/440 V AC  kA    15     10               15               10               15              10
 289/500 V AC  kA    5      5                5                5                5               5
 400/690 V AC  kA    3      3                3                3                3               3
 Rated impulse withstand voltage (1.2/50) Uimp    kV    6
 Dielectric test voltage at ind. freq. for 1 min.    kV    2.5
 Thermomagnetic release     B: 3 In ≤ Im ≤ 5 In       n   n   n   n            n               n
 characteristic
  C: 5 In ≤ Im ≤ 10 In       n   n           n                n                n               n
  D**: 10 In ≤ Im ≤ 20 In    n   n           n                n                n               n
  K**: 8 In ≤ Im ≤ 14 In       n             n                                 n
 Surge current resistance acc. to VDE 0432 Part 2 (wave 8/20)    A    NA  NA  5000  5000  3000  3000
 Mechanical    Toggle       black (MCB) sealable in ON-OFF position + blue (RCD) operating just from OFF position
 features    Electrical life       10000
 Mechanical life       20000
 Protection degree     housing       IP4X
  terminals       IP2X
 Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30  °C/RH    28 cycles with 55°C/90-96% and 25°C/95-100%
 Ambient temperature (with daily average ≤ + 35 °C)    °C    -25…+60
 Storage temperature    °C    -40…+70
 Installation    Terminal size for cables   flexible  mm     6…50
 2
 2
 rigid  mm     6…70
 Tightening torque   Nm  min. 3 / max. 4
 Mounting  on DIN rail EN 60715 (35 mm) by means of rapid fixing device
 Dimensions    Dimensions (H x D x W)    2P  mm    108,2 x 82,3 x 133.5
 and weight       3P  mm    108,2 x 82,3 x 196

 4P  mm    108,2 x 82,3 x 223
 Weight     2P  g  790
 3P  g    1140
 4P  g    1440
 Combination   Combinable with:     auxiliary contact    yes
 with       signal contact/auxiliary   yes
 auxiliary    switch
 elements
  shunt trip    yes
  undervoltage release    yes

 * 1A on 2P and 4P versions, while 0.3A only on 4P ones.
 ** as specified in standard IEC/EN 60947-2 the device withstands Im ≤ 6 In with guaranteed non intervention
   312   313   314   315   316   317   318   319   320   321   322