P. 332
2/140 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
2
DSE201 M
Technical features and overall dimensions
Electrical features
Standards IEC 61009-1 ; IEC 61009-2-2; BS EN 61009-1; AS/NZS
61009
Type (wave form of the earth leakage sensed) AC, A
Number of poles 1P+N
Rated current I A 6≤ In ≤ 50
n
Rated sensitivity I Δn mA 10-30-100-300
Rated voltage U V 230-240
e
Insulation voltage U i V 500 V AC
Overvoltage category III
Pollution degree 2
Max. operating voltage V 264
Min. operating voltage for protection against IΔn V 85
residual sinusoidal alternating currents
Operating voltage of circuit test V 195-264
Rated frequency Hz 50/60
Rated breaking capacity acc. to IEC 61009 ultimate I A 10000
cn
Rated breaking capacity acc. to IEC 60947-2 ultimate I cu kA 15 ( for 6A ≤ In ≤ 40A)
kA 10 (for In = 50A)
service I cs kA 7.5
Rated residual breaking capacity I kA 10
Δm
Rated impulse withstand voltage (1.2/50) U imp kV 4 kV (test voltage 6.2kV at sea level, 5kV at 2000m)
Dielectric test voltage at ind. freq. for 1 min. kV 2.5 kV (50 / 60Hz, 1 min.)
Thermomagnetic release - characteristic B: 3 I ≤ I ≤ 5 I n
n m n
C: 5 I ≤ I ≤ 10 I n n
m
n
Surge current resistance (wave 8/20) A NA
Mechanical data
Housing insulation group II, RAL 7035
Toggle insulation group II, black, sealable in ON-OFF positions
Earth fault indicator blue window
Contact position indication green/red Window
Electrical life operations 10000
Mechanical life operations 20000
Protection degree in enclosure with IP40
cover
terminals IP20
Shock resistance acc. to IEC/EN 60068-2-27 30g - 2 shocks - 13ms
Vibration resistance acc. to IEC/EN 60068-2-6 0.35mm or 5g - 20 cycles at 5…150…5 Hz without load
Environmental conditions (damp heat) °C/RH 28 cycles with 55°C/90-96% and 25°C/95-100%
acc. to IEC/EN 60068-2-30
Reference temperature for setting of thermal °C 30
element
Ambient temperature °C -25…+55
(with daily average ≤ +35 °C)
Storage temperature °C -40…+70