Page 332 - Din prodcuts 2020
P. 332

2/140            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
  2
          DSE201 M
          Technical features and overall dimensions




          Electrical features
          Standards                                                   IEC 61009-1 ; IEC 61009-2-2; BS EN 61009-1; AS/NZS
                                                                      61009
          Type (wave form of the earth leakage sensed)                AC, A
          Number of poles                                             1P+N
          Rated current I                                    A        6≤ In ≤ 50
                     n
          Rated sensitivity I Δn                             mA       10-30-100-300
          Rated voltage U                                    V        230-240
                     e
          Insulation voltage U i                             V        500 V AC
          Overvoltage category                                        III
          Pollution degree                                            2
          Max. operating voltage                             V        264
          Min. operating voltage for protection against IΔn   V       85
          residual sinusoidal alternating currents
          Operating voltage of circuit test                  V        195-264
          Rated frequency                                    Hz       50/60
          Rated breaking capacity acc. to IEC 61009  ultimate I  A    10000
                                                      cn
          Rated breaking capacity acc. to IEC 60947-2  ultimate I  cu  kA  15 ( for 6A ≤ In ≤ 40A)
                                                             kA       10 (for In = 50A)
                                               service I cs  kA       7.5
          Rated residual breaking capacity I                 kA       10
                                   Δm
          Rated impulse withstand voltage (1.2/50) U imp     kV       4 kV (test voltage 6.2kV at sea level, 5kV at 2000m)
          Dielectric test voltage at ind. freq. for 1 min.   kV       2.5 kV (50 / 60Hz, 1 min.)
          Thermomagnetic release - characteristic  B: 3 I  ≤ I  ≤ 5 I  n
                                                  n  m   n
                                               C: 5 I  ≤ I  ≤ 10 I n  n
                                                     m
                                                  n
          Surge current resistance (wave 8/20)               A        NA
          Mechanical data
          Housing                                                     insulation group II, RAL 7035
          Toggle                                                      insulation group II, black, sealable in ON-OFF positions
          Earth fault indicator                                       blue window
          Contact position indication                                 green/red Window
          Electrical life                                    operations 10000
          Mechanical life                                    operations 20000
          Protection degree                    in enclosure with      IP40
                                               cover
                                               terminals              IP20
          Shock resistance acc. to IEC/EN 60068-2-27                  30g - 2 shocks - 13ms
          Vibration resistance acc. to IEC/EN 60068-2-6               0.35mm or 5g - 20 cycles at 5…150…5 Hz without load
          Environmental conditions (damp heat)               °C/RH    28 cycles with 55°C/90-96% and 25°C/95-100%
          acc. to IEC/EN 60068-2-30
          Reference temperature for setting of thermal       °C       30
          element
          Ambient temperature                                °C       -25…+55
          (with daily average ≤ +35 °C)
          Storage temperature                                °C       -40…+70
   327   328   329   330   331   332   333   334   335   336   337