          Residual current relays
          RD3




                                    Technical features      RD3/RD3-48        RD3M/RD3M-48      RD3P/RD3P-48
                                    Operating voltage       RD3: 230-400 Vac   RD3M: 230-400 Vac   RD3P: 230-400 Vac
                                                            +10% / -15%       +10% / -15%       +10% / -15%
                                                            RD3-48: 12-48 Vac/  RD3M-48: 12-48 Vac/  RD3P-48: 12-48 Vac/
                                                            Vdc +10% / -15%   Vdc +10% / -15%   Vdc +10% / -15%
                                    Auxiliary supply frequency  50-60 Hz
                                    Frequency filter        -                 Yes               Yes
          RD3
                                    Type                    A (up to IDn=5 A)
                                                            AC (for higher current)
                                    Operating temperature   -25….+70 °C
                                    Power consumption       <3.6 W (RD3, RD3M, RD3P),
                                                            <600 mW RD3-48, RD3M-48, RD3P-48)
                                    Sensitivity settings IDn  0.03-0.1-0.3-0.5-1-2-3-5-10-30 A
                                    Tripping time settings Dt  0-0.06-0.2-0.3-0.5-1-2-3-5-10 s
                                    Pre-alarm threshold     -                 60%               60%
                                    Max. resistance connection   3 Ω
                                    between toroidal transfor-
                                    mer and relay
          RD3M
                                    Max. length connection of    15 m
                                    remote reset button
                                    Output Contact capacity    8 A, 250 V a.c.
                                    (7-8-9); (10-11-12)
                                    Led bar indicator       -                 -                 Yes
                                    Max. cable terminals section 2.5 mm²
                                    Modules                 3
                                    Dimensions              52.8 × 85 × 64.7 mm
                                    Protection degree       IP20
                                    Standards               IEC/EN 60947-2 annex. M; IEC/EN 62020
          RD3P
                                    RD3 residual current relays
                                    The RD3 family of electronic residual current relays provides residual current protection
                                    and monitoring functions according to IEC/EN 60947-2:2006 annex M when used in
                                    conjunction with external toroids belonging to TR family, all S 200 miniature circuit
                                    breakers and Tmax/XT range moulded case devices up to T5/XT4, for industrial installations.
                                    The RD3 residual current relays can provide status indications through two output contacts.

                                    Operating voltage     Bbn    Order details                Price  Weight Pack
                                                          8012542                             1 piece 1 piece unit
                                    [V]                   EAN    Type code     Order code           [kg]  pc.
                                    12-48 a.c./d.c.       748236  RD3-48       2CSJ201001R0001      0.13  1
                                    230-400 a.c.          734833  RD3          2CSJ201001R0002      0.25  1
                                    12-48 a.c./d.c.       733935  RD3M-48      2CSJ202001R0001      0.13  1
                                    230-400 a.c.          747031  RD3M         2CSJ202001R0002      0.25  1
                                    12-48 a.c./d.c.       734734  RD3P-48      2CSJ203001R0001      0.13  1
                                    230-400 a.c.          733836  RD3P         2CSJ203001R0002      0.25  1