2/148            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
  2
          Front panel residual current relays
          ELR




          Technical features            ELR48P     ELR72     ELR72P    ELR96      ELR96P    ELR96PF    ELR96PD
          Operating voltage        [V]  24, 48,    24, 48,   24, 48, 110   24, 48, 110,   24, 48, 110,   110, 230,   110,
                                        110, 230   110, 230   230, 400   230, 400   230, 400   400 a.c.  230, 400
                                        a.c./      a.c./     a.c./     a.c./      a.c./                a.c.
                                        24, 48, 115   24, 48, 110   24, 48 d.c.  24, 48, 110   24, 48 d.c.
                                        d.c.       d.c.                d.c.
          Frequency                [Hz]  50 – 60
          Frequency filter              -          -         -         -          -         Yes        Yes
          Type                          A
          Operating temperature    [°C]  -10…+60
          Power consumption        [W]  <7
          Sensitivity setting I∆n  [A]  from 0,03 to 30
          Tripping time setting Dt  [s]  from 0 to 5
          Contacts                 [no.]  2        1         2         1          2         2          2
          Contact capacity         [A]  5 (250 V a.c.)
          Dimensions               [mm] 48 x 48    72 x 72   72 x 72   96 x 96    96 x 96   96x96      96 x 96
          Digital display               -          -         -         -          -         -          Yes
          Protection degree (with cover)  IP52
          Protection degree (without    IP40
          cover)
          Protection degree (terminals)  IP20
          Standards                     IEC EN 60947-2
                                        Annex M