Page 371 - Din prodcuts 2020
P. 371

4/17




          —
          Auxiliary elements for
          MCBs S 200, SN 201, RCDs F 200, DS 200, DS201-DS202C, DS203NC,
          DSE201 M, AFDD S-ARC1 and Switch disconnectors SD 200 series

                                                                                                                       4
                                     Shunt trip for S 200 MCBs
                                                                     S2C-A1
                                    Rated voltage       AC     V     12…60
                                                        DC     V     12…60
                                    Max release duration       ms    <10 @ Rated voltage
                                    Min. release voltage  AC   V     8.4
                                                        DC     V     8.4
               S2C-A                Power consumption   Ub     V     12     12     24     24     60      60
                                                                     DC     AC     DC     AC     DC      AC
                                                        Ib max  A    2.2    2.5    4.5    5      14      8.8
                                    Coil resistance            Ω     3.7
                                    Terminals                        Fale-safe bi-directional cylinder-lift-terminal
                                    Tightening torque          Nm    2.8
                                    Dimensions (H x D x W)     mm    85 x 69 x 17.5
                                                                     S2C-A2
                                     Rated voltage      AC     V     110…415
                                                        DC     V     110…250
                                     Max release duration      ms    <10 @ Rated voltage
                                     Min. release voltage  AC  V     77
                                                        DC     V     77
                                     Power consumption  Ub     V     110    110    220    230     415
                                                                     DC     AC     DC     AC      AC
                                                        Ib max  A    0.4    0.5    1.1    1.0     2.7
                                    Coil resistance            Ω     225
                                    Terminals                        Fale-safe bi-directional cylinder-lift-terminal
                                    Tightening torque          Nm    2.8
                                    Dimensions (H x D x W)     mm    85 x 69 x 17.5

                                    Shunt trips
                                    Function: remote opening of the device when a voltage is applied. Suitable for MCBs S 200
                                    series, RCBOs DS 200 series, SD 200 switch disconnectors series.
                                    Shunt trips use a coil like MCBs for tripping. To trip a shunt it is necessary to choose the
                                    right voltage and make sure the corresponding Ibmax (as mentioned in the table above) is
                                    provided by the power supply used. If the power supply can provide higher currents the
                                    shunt trip will reduce the current to Ibmax due to its internal resistance.
                                    As soon as the shunt tripped, the contact inside is open – the electrical circuit is discon-
                                    nected even if the shunt trip is still powered on. The free-tripping mechanism of the shunt
                                    trip allows a restart of the MCB only after the shunt trip gets no external release signal any-
                                    more.

                                    Rated voltage         Bbn     Order details                Price Weight Pack
                                                          4016779                             1 piece 1 piece unit

                                                          EAN     Type code   Order code            kg    pc.
                                    AC/DC 12…60 V         570992  S2C-A1      2CDS200909R0001       0.15  1
                                    AC 110…415 V/DC110…250 V  571005  S2C-A2  2CDS200909R0002       0.15  1