Page 416 - Din prodcuts 2020
P. 416
4/62 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
Auxiliary elements for
S750 DR series
4
S750DR-AUX
Electrical data
Standards DIN EN 62019 (VDE 0640), IEC/EN 62019
DIN EN 60947-5-1 (VDE 0660-200), IEC/EN 60947-5-1
Conventional free air thermal 6 A
current Ith
Utilisation categories AC14 AC15 DC12 DC13
Ue 400 V 230 V 400 V 230 V 250 V 125 V 60 V 24 V
Ie (max) 2 A 6 A 2 A 6 A 0.5 A 1.5 A 2 A 4 A
Rated insulation voltage U 690 V AC
acc. to IEC/EN 60664-1
Overvoltage category IV
Pollution Degree 3
Protection degree acc. to IP20
IEC/EN 60529
Min. switching power DC 5V DC/5 mA, 12V DC/5 mA
Rated impuls withstand 6 kV
voltage Uimp (1.2/50 μs)
Installation
Cross-section 1 conductor 0.75 - 2.5 mm² solid, flexibel with and without insulated ferrule conductors
of 2 conductor 2 x 0.75 - 2 x 2.5 mm² solid, flexibel with and without insulated ferrule
Tightening torque 0.8 Nm
Mechanical data
Vibration resistance 5 g, 20 cycles at 5 ...150...5 Hz with 24 V AC/DC, 5 mA, without switching
according to IEC/ operation
EN 60 068-2-6
Mechanical endurance 10,000 ops.
Pole dimensions (H x D x W) 128 x 77 x 8.7
Mounting
Only 1 auxiliary contact mountable on the right site
Not mountable to S751DR/3