Page 416 - Din prodcuts 2020
P. 416

4/62             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Auxiliary elements for
          S750 DR series




  4
                                    S750DR-AUX
                                    Electrical data
                                    Standards            DIN EN 62019 (VDE 0640), IEC/EN 62019
                                                         DIN EN 60947-5-1 (VDE 0660-200), IEC/EN 60947-5-1
                                    Conventional free air thermal  6 A
                                    current Ith
                                    Utilisation categories   AC14       AC15          DC12          DC13
                                                Ue       400 V   230 V   400 V   230 V   250 V   125 V   60 V   24 V
                                                Ie (max)   2 A   6 A    2 A    6 A    0.5 A   1.5 A   2 A   4 A
                                    Rated insulation voltage U   690 V AC
                                    acc. to IEC/EN 60664-1
                                    Overvoltage category   IV
                                    Pollution Degree     3
                                    Protection degree acc. to   IP20
                                    IEC/EN 60529
                                    Min. switching power DC   5V DC/5 mA, 12V DC/5 mA
                                    Rated impuls withstand   6 kV
                                    voltage Uimp (1.2/50 μs)
                                    Installation
                                    Cross-section   1 conductor  0.75 - 2.5 mm² solid, flexibel with and without insulated ferrule conductors
                                    of          2 conductor  2 x 0.75 - 2 x 2.5 mm² solid, flexibel with and without insulated ferrule
                                    Tightening torque    0.8 Nm
                                    Mechanical data
                                    Vibration resistance   5 g, 20 cycles at 5 ...150...5 Hz with 24 V AC/DC, 5 mA, without switching
                                    according to IEC/    operation
                                    EN 60 068-2-6
                                    Mechanical endurance   10,000 ops.
                                    Pole dimensions (H x D x W)   128 x 77 x 8.7
                                    Mounting
                                                         Only 1 auxiliary contact mountable on the right site
                                                         Not mountable to S751DR/3
   411   412   413   414   415   416   417   418   419   420   421