Page 510 - Din prodcuts 2020
P. 510

5/66             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          OVR PV surge protective devices Photovoltaic networks




          Technical features
          Types                            OVR PV T2 40-    OVR PV T2 40-                      OVR PV T2 40-
                                           600  P QS        1000 P QS                          1500 P QS
  5
          with auxiliary contact (TS)      OVR PV T2 40-    OVR PV T2 40-     OVR PV T2 40-1000   OVR PV T2 40-
                                           600  P TS QS     1000 P TS QS      P TS TWIN QS     1500 P TS QS
          Technology                       Varistor         Varistor          Varistor         Varistor
          Electrical features
          Standard                         IEC 61643-11/    IEC 61643-11/     IEC 61643-11/    IEC 61643-11/
                                           EN 61643-11/     EN 61643-11/      EN 61643-11/     EN 61643-11/
                                           UL 1449 4th Ed   UL 1449 4th Ed    UL 1449 4th Ed   UL 1449 4th Ed
          Type/test class                  T2/II            T2/II             T2/II            T2/II
          Protected lines                  2                2                 4                2
          Types of networks                Photovoltaic     Photovoltaic      Photovoltaic     Photovoltaic
          Type of current                  DC               DC                DC               DC
          Nominal voltage Un (L-N/L-L)  [V]  600            1000              1000             1500
          Max. cont. operating voltage Ucpv  [V]  600       1100              1100             1500
          Max.cont.operating voltage   [V]  600             1100              1100             1500
          according    (MCOV)
          Impulse current Iimp (10/350)    2                -                 2                2
          Maximum discharge current   [kA]  40              40                40               40
          Imax (8/20)
          Nominal discharge current In (8/20)  [kA]  20     20                20               10
          Voltage protection level Up at In   [kV]  2.8/1.4  3.8/3.8          3.8/3.8          4.5/4.5
          (L-L/L-PE)
          Voltage protection rating according  [kV]  1.2/1.2/1.8  2.5/2.5/2.5  2.5/2.5/2.5      4/4/4
             (VPR (L+/G, L-/G, L+/L-))
          Response time             [ns]   ≤ 25             ≤ 25              ≤ 25             ≤ 25
          Residual current IPE      [µA]   ≤10              ≤1000             ≤1000            ≤1000
          Short-circuit DC current Iscpv  [A]  300          10,000            10,000           10,000
          Short circuit withstand    [kA]  10               10                10               10
          according    (S CCR )
          Disconnector  Fuse               no need up to 0.3 kA  no need up to 10 kA  no need up to 10 kA  no need up to 10 kA
                       Circuit breaker     no need up to 0.3 kA  no need up to 10 kA  no need up to 10 kA  no need up to 10 kA
          Pluggable cartridge              Yes              Yes               Yes              Yes
          Integrated specific thermal      Yes              Yes               Yes              Yes
          disconnector
          State indicator                  Yes              Yes               Yes              Yes
          Safety reserve                   No               No                No               No
          Auxiliary contact                Yes (TS option)  Yes (TS option)   Yes (TS option)  Yes (TS option)
          Installation
          Wire range   Solid wire   [mm²]  2.5…35           2.5…35            2.5…35           2.5…35
          (L, N, PE)   Stranded wire  [mm²]  2.5…25         2.5…25            2.5…25           2.5…25
          Stripping length (L, N, PE)      12.2             12.2              12.2             12.2
          Tightening torque (L, N, PE)     2.5              2.5               2.5              2.5
          Auxiliary contact (TS)
          Contact complement               1 NO - 1 NC      1 NO - 1 NC       1 NO - 1 NC      1 NO - 1 NC
          Minimum load                     12 V DC - 10 mA  12 V DC - 10 mA   12 V DC - 10 mA  12 DC - 10 mA
          Maximum load                     250 V AC - 1 A   250 V AC - 1 A    250 V AC - 1 A   250 V AC - 1A
          Connection cross-section         1.5              1.5               1.5              1.5
          Miscellaneous characteristics
          Stocking and operating temperature [°C]  -40 to +80  -40 to +80     -40 to +80       -40 to +80
          Maximal Altitude          [m]    5000             5000              5000             5000
          Humidity Rate HR                 95%              95%               95%              95%
          Degree of protection             IP20             IP20              IP20             IP 20
          Fire resistance according to UL 94  V0            V0                V0               V0
          Dimensions   height x width x   [mm]  88 x 53.4 x 65  88 x 53.4 x 65  88 x 88,33 x 65  88 x 53.4 x 65
                       depth        [inches]  3.46 x 2.10 x 2.56  3.46 x 2.10 x 2.56  3.46 x 3,5 x 2.56  3.46 x 2.10 x 2.56
          with auxiliary   height x width x   [mm]  95 x 53.4 x 65  95 x 53.4 x 65  95 x 88,33 x 65  95 x 53.4 x 65
          contact (TS)  depth       [inches]  3.46 x 2.10 x 2.56  3.77 x 2.1 x 2.55  3.46 x 3,5 x 2.56  3.46 x 2.10 x 2.56
          Replacement Cartridges
          Phase Product ID                 OVR PV T2 40-600 C QS OVR PV T2 40-1000 C QS OVR PV T2 40-1000 C QS OVR PV T2 40-1500 C QS
                                           2CTB804153R3100  2CTB804153R3200   2CTB804153R3200  2CTB804153R3300
                                           OVR PV MC C QS
                                           2CTB804153R3500