Page 515 - Din prodcuts 2020
P. 515
5/71
—
Protection and safety
OVR WT surge protective devices - Wind turbine networks
Due to their height, wind turbines have especially high exposure to lightning, they need high
capacity and reliable lightning and surge protection.
The OVR WT family takes into consideration the specificity of wind installations with 5
a high peak repetitive voltage withstand (Urp up to 3 kV) ensure a safe protection to Wind
applications.
It can be DIN mounted with the OVR.
OVR WT 3L 690 P TS
Type 1+2 WT
Pro- Impulse Max. Nomi- Volt- Max. Bbn Order details Weight
tected current dis- nal age cont. 1 piece
lines Iimp charge current pro- oper-
10/350 current In tec- ating
Imax tion volt-
8/20 level age
Up Ucpv
kA kA kA kV V 366030 Type code Order code kg
3 2 40 20 6 400/ 518507 OVR WT 3L 690 P 2CTB235402R0000 1.67
690 TS
3 2 40 20 6 400/ OVR WT 3L 690 P 2CTB235401R0000 2.5
690 (enclosed)
OVR WT 3L 690 P