Page 707 - Din prodcuts 2020
P. 707

6/75




          —
          Command and signaling
          CP-D primary switch mode power supplies




         2CDC 271 024 F0b07         Technical features              CP-D   CP-D    CP-D   CP-D   CP-D    CP-D

                                                                    12/0.83
                                                                                   24/0.42
                                                                                          24/1.3
                                                                           12/2.1
                                                                                                         24/4.2
                                                                                                 24/2.5
                                    Input circuit
                                    Rated input voltage U in  [V AC]  100-240
                                    Input voltage range      [V AC]  90-264
                                                                                                                       6
                                                             [V DC]  120-375
                                    Frequency range          [Hz]   47-63
          CP-D                      Hold-up time             [ms]   min. 30  min. 30  min. 30  min. 30  min. 60  min. 60
                                    Internal input fuse, slow-acting   [A]  1  2   1      2      2       3.15
                                    (250 V AC)
                                    Typical power   at 230 V AC  [W]  13   31      12     38     70      114
                                    dissipation
                                    Inrush current limiting (max 3 ms)  [A]  30  50  30   50     60      60
                                    Output circuit
                                    Rated output voltage     [V DC]  12    12      24     24     24      24
                                    Tolerance of the output         ±1%
                                    Adjustment range of the output   [V DC]  -  -  -      24-28  24-28   24-28
                                    voltage
                                    Rated output current I r  [A]   0.83   2.10    0.42   1.30   2.50    4.20
                                    Rated output power       [W]    10     30      10     30     60      100
                                    Resistance to reverse feed  [V DC]  18 / 1 s  18 / 1 s  35 / 1 s  35 / 1 s  35 / 1 s  35 / 1 s
                                    Parallel connection             Yes, using CP-D RU
                                    Series connection               Allowed, to increase voltage
                                    Output circuit: no-load, overload, and short-circuit behaviour
                                    Characteristic curve of output  U/I characteristic curve
                                    Short-circuit behavior          continuous short-circuit stability
                                    Overload protection             output power limiting
                                    No-load protection              continuous no-load stability
                                    Currrent limiting at short circuit  [A]  typ 1.4  typ 5.9  typ 0.78  typ 4.2  typ 6.05  typ 11.5
                                    LED status indicator
                                    Green LED (DC ON)               Output voltage applied
                                    Red LED (DC LOW)                Output voltage too low
                                    Operating temperature    [°C]   -40…+70
                                    Derating of the output current  2.5% / °C
                                    60°C < Ta ≤ 70 °C
                                    Approval / Marks                cULus, cURus, CCC, EAC, CE, RCM
                                    (depending on device)