Page 726 - Din prodcuts 2020
P. 726
7/10 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
Control and automation
E 232 staircase lighting time-delay switches
Technical features
E 232-230 E 232E-230N E 232E-8/230N E 232E-230 Multi E 232E-8/230 Multi
10 10
Time range (stepless) 1 – 7 min. 0.5 – 20 min. 0.5 – 20 min. 0.5 – 20 min. 0.5 – 20 min.
in 15 sec. stepless stepless stepless stepless
increments
Control voltage 230 V AC n n n n n
Universal voltage in addition 8 … 240 V AC/DC 8…240 V AC/DC
Glow lamp load 50 mA 150 mA 150 mA 150 mA 150 mA
3/4 conductor operated switches automatically automatically automatically automatically
7
Resettable n n n n n
Steady-light switch n n n n n
Advance warning acc. DIN 18015-2 n n
Long-time range of 60 min. n n
Multi-functional (10 functions) n n
Rated voltage 230 V AC 240 V AC 240 V AC 240 V AC 240 V AC
Rated Frequency 50Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz
Control voltage range 0.9 ... 1.1 Un 0.85 ... 1.1 Un 0.85 ... 1.1 Un 0.85 ... 1.1 Un 0.85 ... 1.1 Un
Power loss 1 VA 6 VA 6 VA 6 VA 6 VA
Rated switching capacity 16 A, 230 V AC 16 A, 230 V AC 16 A, 230 V AC 16 A, 230 V AC 16 A, 230 V AC
Filament lamps 2,300 W 2,300 W 2,300 W 3,600 W 3,600 W
Halogen lamps 2,300 W 2,300 W 2,300 W 3,600 W 3,600 W
Fluorescent lamps series compensated / 2,300 VA 2,300 VA 2,300 VA 3,600 VA * 3,600 VA *
uncorrected
Fluorescent lamps inductive or capacitive 2,300 VA 2,300 VA 2,300 VA 3,600 VA * 3,600 VA *
Fluorescent lamps shunt compensated 1,300 VA (70 μF) 400 VA (42 μF) 400 VA (42 μF) 1,200 VA (120 μF) * 1,200 VA (120 μF) *
Electronic controlgear 9x7 W, 6x11 W 9x7 W, 7x11 W, 9x7 W, 7x11 W, 34x7 W, 27x11 W, 34x7 W, 27x11 W,
5x15 W, 5x20 W 7x20 W, 7x23 W 7x20 W, 7x23 W 24x15 W, 22x23 W 24x15 W, 22x23 W
Inductive load (cos j = 0.6/230 V AC) 2,300 2,300 2,300 2,300 2,300
Contact material AgSnO2 AgSnO2 AgSnO2 AgSnO2 AgSnO2
Contact gap ≥ 3 mm < 3 mm < 3 mm < 3 mm < 3 mm
Mech. serviceable life > 106 > 107 > 107 > 107 > 107
Serviceable life at rated load, cos j =1 > 105 > 2x105 > 2x105 > 2x105 >2x105
Serviceable life at rated load, > 104 > 4x104 > 4x104 > 4x104 > 4x104
cos j =0.6
Max. terminal cross-section 10.7 mm² 13 mm² 13 mm² 13 mm² 13 mm²
Max. conductor cross-section 6 mm² 4 mm² 4 mm² 4 mm² 4 mm²
ON duration Resettable after 100 % 100 % 100 % 100 %
30 sec.
Ambient temperature – 10 °C to + 50 °C – 25 °C to + 50 °C – 25 °C to + 50 °C – 25 °C to + 50 °C – 25 °C to + 50 °C
Housing and insulation material heat resistant, heat resistant, heat resistant, heat resistant, heat resistant,
self-extinguishing self-extinguishing self-extinguishing self-extinguishing self-extinguishing
thermoplast thermoplast thermoplast thermoplast thermoplast
Control current at 230 V AC 4.5 mA 26 mA 26 mA 26 mA (min. 8 mA 26 mA (min. 8 mA
at 8 V AC) at 8 V AC)
Minimum command duration 10 ms 20 ms 20 ms 20 ms / 50 ms for 20 ms / 50 ms for
multi voltage input multi voltage input
* no disconnection advance warning possible for this application.