Page 817 - Din prodcuts 2020
P. 817
8/77
—
Energy efficiency
TMD temperature control units
Technical features
Auxiliary supply Alternating current [V] 20÷250 ±15%
Direct current [Hz] 115-230-400 50-60
Power consumption [VA] 4 max
Input Sensor PT100 RTD (not included)
Type 3 wires (2 and 4 wires types are also supported)
TMD Error 1 degree every 0,39 W
Measure range [°C] 0...220 ± 2
Compensation [W] 20 max
Trip delay/hysteresis [s/°C] 5/2
Output Number 4
Type NO-CO-NC 8
Vmax [V] 12 d.c.
Imaxww [A] 8 (resistive load)
Functions Alarm, trip, cooling, auto-test
Programmable Alarm, tip, hold, fan, temp. max
functions
Display 7 segments LED
Connections Terminals removable screw
Max section [mm ] 2 2.5
Insulation voltage [V] 2500/50 Hz - 1 min
Protection degree Front IP52
Rear IP20
Operation temperature [°C] -10...+55, relative humidity max 90%
Storage temperature [°C] -25...+80
Reference IEC EN 50081-2, IEC EN 50082-2, IEC EN 60255
Temperature control units
TMD are used measure and control the temperature levels and efficiency of electric
machines, power transformers, motors, etc.
The temperature is measured by four PT100 type sensors. Each measuring channel has
two programmable alarm thresholds which trip two output relays to remotely signal that
a critical temperature has been reached.
The measured values and any alarm conditions are shown on the dual 3-digit display on the
front of the device, which also has five programming keys for configuring its operation.
The control unit is also able to store in memory maximum values and a log of all trip-events.
Temperature Bbn Order details Price Weight Pack
measured 8012542 1 1 piece unit
piece
EAN Type code Order code kg pc.
4 560203 TMD-4/96 2CSG524000R2021 0.8 1