8/82             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Energy efficiency
          CT measurement current transformers with through primary




                                 Technical features
                                                                CT…             CTO            TRFM
                                 Standard secondary current  [A]  5 A
                                 Max. voltage for operation  [kV]  1,2
                                 Test voltage             [kV]  3 a 50 Hz/1min
                                 Residual current voltage at    < 25 V rms
                                 secundary terminals when security
         CT                      circuit intervenes  (only SELV
                                 versions)
                                 Short circuit rated thermal current  [IpN]  40 per 1 sec.  60 per 1 sec.  40 per 1 sec.

                                 Short circuit rated dynamic   [Ith]  2,5 per 1 sec.
                                 current
                                 Permanent overload       [IpN]  1,2
  8
                                 Safety factor            [Fs]  from ≤ 2 to ≤ 10 depending on the type and capacity
                                 Frequency                [Hz]  50-60
                                 Air insulation class           Class E         B              E
                                 Terminals                      primary P1 - P2 (K - L); secondary s1 - s2 (k - l)
                                                                P1 (K) primary winding input
                                                                s1 (k) secondary winding input
                                                                P2 (L) primary winding output
                                                                s2 (l) secondary winding output
                                 Housing                        Self-extinguishing thermoplastic resin V0
                                 Protection degree              IP30            IP20           IP20
                                 Operating temperature    [°C]  -5...+50        -5...+50       -25...+50
                                 Max. temperature on bars  [°C]  70°C
                                 Storage temperature      [°C]  -20...+80       -20...+80      -40...+80
                                 Relative humidity              80%
                                 Reference standard             IEC EN 60044-1, IEC EN 61010-1
                                 Secondary protection circuit   IEC60364;
                                 reference standards (only SELV   IEC473.1.4; IEC556.3;
                                 versions)                      CEI64-8-4;
                                                                CEI411.1.4.3;
                                                                CEI411.5.2; CEI411.2;
                                                                CEI473.1.4;
                                                                CEI473.2.3

                                 CT and CTA current transformers
                                 Used to transform primary currents (max. 6000 A) into .../5 A low secondary currents
                                 indirectly supplying power to analogue and digital measurement devices. They are available
                                 both with wound and through primary. In the first case they are provided along with the bar or
                                 the primary terminal; in the second case they have a hole to insert in the bar or the cable which
                                 forms the primary.
                                 The rated current to the secondary windings is 5 A, in line with the offer of measuring devices.
                                 CT ../1 are not employable with ABB mono-function and multifunction measuring devices. The
                                 use of CT ../1 is needed in case of long wirings from CT secondary windings to the measuring
                                 device; nowadays, the wide use of communication protocols doesn’t require the instrument to
                                 be installed far from the line to measure.
                                 The new SELV versions of the CT PRO XT and CT MAX guarantee maximum safety against
                                 overvoltage and switchboard internal overheating thanks to the innovative electronic
                                 protection circuit which automatically short-circuit the CT secondary winding in case
                                 of accidental disconnection of its secondary terminals.