9/32             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          SMISSLINE TP plug-in system
          Surge arrester





          Type                                            OVR404 4L 40-275 P TS QS   OVR404 3N 40-275 P TS QS
          Technologie                                     varistor                  Varistor/gaz tube (N)
          System network                                  TNS                       TT–TNS

          Electrical features
          Standard                                        IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11
          Type / test class                               Type 2                    Type 2
          Number of pole                                  4                         4
          Nominal voltage UN (L-N, L-L)                   240/415 V                 240/415 V
          Type of voltage                                 a. c. 45–65 Hz            a. c. 45–65 Hz
          Max. cont. operating voltage U c                275 V AC                  275 V AC
          Nominal discharge current I  (8/20)             20 kA                     20 kA
                            n
          Maximum discharge current I max  (8/20)         40 kA                     40 kA
          Maximum impulse current I imp  (10/350)         2 kV                      2 kA
          Voltage protection level U  at I  (L-N / N-PE / L-PE)  1.5 kV             1.25/1.4/1.5 kV
                           p  n
          Voltage protection level U  at 3 kA (L-N / N-PE / L-PE)  0.5 kV           0.8/1.4/0.85 kV
                           p
  9
          Voltage protection level U  at 5 kA (L-N / N-PE / L-PE)  0.7 kV           0.85/1.4/0.95 kV
                           p
          Voltage protection level U  at 10 kA (L-N / N-PE / L-PE)  0.9 kV          1/1.4/1.15 kV
                           p
          TOV (Temporary overvoltage) withstand U  (L-N: 5s./N-PE: 200 ms)  337/- V   337/1200 V
                                      t
          Response time Response time                     ≤ 25 ns                   ≤ 25 ns
          Short-circuit withstand capability Isccr        100 kA                    100 kA
          Back up prootection circuit breaker             ≤ 125 A; S800S B          ≤ 125 A; S800S B
          Pluggable cartridge                             Yes                       Yes
                        ®
          Integrated QuickSafe  technology                Yes                       Yes
          State indicator                                 Yes                       Yes
          Auxiliary contact (TS)                          Yes                       Yes
          Installation
          Wire range (L, N, PE)                           2.5…25 mm²                2.5…25 mm²
                                                          cable or rope             cable or rope
          Connection cross-section                        2.5…16 mm² litz wire with ferrule   2.5…16 mm² litz wire with ferrule
          Tightening torque                               2.8 Nm                    2.8 Nm

          Auxiliary contact (TS)
          Contacts information                            1 NO – 1 NC               1 NO – 1 NC
          Max. load/current                               12 V DC – 10 mA           12 V DC – 10 mA
          Min. load/current                               250 V AC – 1 A            250 V AC – 1 A
                                                          1.5 mm²                   1.5 mm²

          Operating temperature                           –25 °C – +60 °C           –25 °C – +60 °C
          Stocking temperature                            –25 °C – +80 °C           –25 °C – +80 °C





          Back up protection

          Typ 2 QuickSafe®          Prospective short circuit   Circuit breaker maximum ratings 1)  Fuse 2)
          Surge Protective Devices  current at SPD location (Ip)  curve B or C           (gL - gG)
          Maximum ratings
          I : 5, 20, 30 kA          0,625 kA < I  < 100 kA     S800S B or C – 125 A      125 A fuse
                                                                             2)
                                            p
          n
          U : 275, 350, 440, 600 V
           c
          1)  Maximum ratings, must be in accordance with the installation to follow coordination rules with main or upstream short circuit protection(s).
          2)  up to Ip ≤ 50 kA